Specifications
Cable Connections
Installation Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME-INSTALL/DGB Rev. E, 2011-08-16,
Autronica Fire and Security AS
Page 32
J1-x Description Internal External
10
Monitored
Input 2
User
configurable
input.
Monitored
for open and
short
circuit.2k
resistor to
0V.
Activates at
910 ohm to
0V.
11
Monitored
Input 0V
0V reference
for
Monitored
Inputs 1 & 2
12
Monitored
Output 1
+24V
0,5 A
resettable
fuse.
13
Monitored
Output 1
0V
14
Monitored
Output 2
+24V
0,5 A
resettable
fuse.
Default
configured
as Fire
Alarm
Device
Output.
Monitored
for short and
open circuit.
2kohm end
resistor. Max
500mA.
15
Monitored
Output 2
0V
16
Open
Collector
Output 1
User
configurable
Open
collector
output.
Non-
monitored
Switches to
0V at
activation.
Max.0,5A
17
Open
Collector
Output 2
User
configurable
Open
collector
output.
Non-
monitored
Switches to
0V at
activation.
Max.0,5A
9
10
11
+24V
0V
+24V
0V
12
13
14
15