Specifications

Cable Specifications
Installation Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME-INSTALL/DGB Rev. E, 2011-08-16,
Autronica Fire and Security AS
Page 21
Panel 3
(BS-210/BU-210
etc)
Cable 2b
Redundant Power between external panels
Panel 1
(BSA-200/J1)
Terminals
Not connected Pair 1 Not
connected
J13/3 24V IN 2 Pair 2 (both wires) 24V IN 2 J14/3
J13/4 0V IN 2 Pair 3 (both wires) 0V IN 2 J14/4
Not connected Pair 4 Not
connected
Panel 2
(BS-210/BU-210
etc)
Cable 3
From last external panel and back to Fire
Alarm Control Panel
Panel 1
(BS-200)
Terminals
J13/5 A_1 Pair 1+ BU/BV A2 J4/18
J13/6 B_1 Pair 1- BU/BV B2 J4/19
J13/3 24V IN 2 Pair 2 (both wires) O.P. +24V 2 J1/7
J13/4 0V IN 2 Pair 3 (both wires) O.P. 0V 2 J1/8
Not connected Pair 4 Not
connected
See drawing, chapter 9.10.