Specifications
Cable Specifications
Installation Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME-INSTALL/DGB Rev. E, 2011-08-16,
Autronica Fire and Security AS
Page 17
Maximum
resistance /
capacitance
Wire
Dimensions
(examples)
Maximu
m cable
length
Remarks
( / μF)
(mm
2
) (AWG) (m)
Panel Bus
Capacitance pr. 1km cable
Capacitance < 200 nF
Capacitance < 100 nF
Maximum cable segment length
< 600 m
< 1000 m Cat 5 or better
Cable shall be twisted pair, characteristic
impedance 100 ohm.
Panel Bus
Power supply
2-wire 24V supply:
Calculation vs power loss
The power loss in these cables has to take into consideration the maximum current at
startup due to the Lamp test, which is 300 mA. Cable loss shall be limited to ensure at
least 18V supply to each panel in this situation.
RS 232
For cabinet internal connections only, limited to 10m.
For USCG installations the length is limited to 6m (20 feet).
RS485/422
Shielded cable is required if cable is >3m. Cable shall be twisted pair, 100 ohm
characteristic impedance (Cat 5 cable recommended).
For USCG installations the length is limited to 6m (20 feet).
If multi-stranded cables are used, cable crimps shall be used.
8.2 Detection Loop Cables
8.2.1 General Considerations
The maximum cable length is determined by both cable loss and the
at-site designed power consumption. Increasing current implies a
demand for less cable loss, hence increased copper area or reduced
cable length (refer to Guidance Table on the next page).
In the system service menu (Unit Configuration/Detection Loops) it is
possible to limit the maximum possible current consumption for a
selected detection loop. There are 4 different settings, 100mA (the
default setting), 150mA, 200mA and 250mA. The current consumption
per device is found in the data sheets of the respective units.
Note: The current consumption of LED indicators (on detectors or loop
units) in the event of an alarm has to be included.
The current consumption of other loads has to be included (for
example, loads applied to the output connection of detectors).
Units with varying current consumption, like sounders or strobe
devices have to be included according to the configured setting, for
example, the sound level may vary.