8. Cable Specifications
8.1 Overview
The table below gives the wire dimension in square millimeters or
AWG (American Wire Gauge) for various cable lengths. Please refer
to national/local standards for your country. Data may change. Please
check with your local manufacturer.
Maximum
resistance /
capacitance
Wire
Dimensions
(examples)
Maximum
cable
length
Remarks
( / μF)
(mm
2
) (AWG) (m)
Detection Loop
(Loop current)
0,5
μF
Setting :
100mA
(both conductors )
50
2 x 0,75
2 x 1,0
2 x 1,5
2 x 2,5
18
17
15
13
1000 m
1300 m
2000 m
3300 m
150mA
31
2 x 0,75
2 x 1,0
2 x 1,5
2 x 2,5
18
17
15
13
600 m
800 m
1200 m
2050 m
200mA
20
2 x 0,75
2 x 1,0
2 x 1,5
2 x 2,5
18
17
15
13
400 m
500 m
800 m
1300 m
250 mA
13
2 x 0,75
2 x 1,0
2 x 1,5
2 x 2,5
18
17
15
13
250 m
350 m
500 m
850 m
Inputs,
Monitored
10m
Inputs,
Non-monitored
50m
Output,
Monitored
(Alarm
Sounder
Circuits)
-
-
2 x 1,5
2 x 0,78
15
18
-
-
Determined by cable loss
(0,5A maximum load)
Output, Relay
-
Output, O.C
100m
Battery
-
-
-
2 x 2,5
2 x 1,5
13
5 m
3m
Maximum battery cable length is
5m
Maximum cable resistance is
0.05 ohm
Mains
- 3 x 1,5 15 - -