User guide

Operating the Tool
User Guide AutroClient, Autroprime Interactive Fire Detection System, 116-P-APRIME2-AUTCLI/LGB, 2012-06-15,
Autronica Fire and Security AS
Page 20
1 Any State: One unit in any state will activate the outputs in the
activation group. Any state is input state, fault state or disable state;
the input state depends on the type of activation group. For an input
activation group the input state is ON, for a point activation group the
input state is either Alarm, PreAlarm, AlarmTest or PreAlarmTest.
1 Input State: One unit in input state will activate the outputs in the
activation group. Units in fault or disable state will not activate the
outputs.
2 Input OR 1 Input + 1 Any State: Two units in input state or one
unit in input state and one unit in any state will activate the outputs in
the activation group. Thus, the activation group must always have one
unit in input state to activate. For a point activation group one of the
points must be in alarm state to activate the activation group.
The Activation Group view also has got a filter option which is used to
filter activation group by name or units connected to activation groups
by name, function or hardware and it is case-insensitive. The filter is
very useful for large configurations.
There is also a filter function to find Detection Zones that has no
relation to an Alarm Zone, to display this select a Detection Zone
activation group and select the input and type in “missing az” as filter.
The Detection Zones with no Alarm Zone activation will be displayed.
Figure 21. AutroClient cause/effect view, displaying voting options for a Point Activation
Group.