User guide
Operating the Tool
User Guide AutroClient, Autroprime Interactive Fire Detection System, 116-P-APRIME2-AUTCLI/LGB, 2012-06-15,
Autronica Fire and Security AS
Page 17
To create a new activation group type in a name and select a
function from the following options:
Input activation: Inputs activating outputs
Point activation: Points activating outputs
DZ activation: Detection Zones activating Alarm Zones and/or
outputs.
AZ neighbour activation: Alarm Zones neighbour / alert activation.
Output activation: Outputs activating other outputs.
After adding an activation group, the activation group will be displayed
in the panel’s tree view and in the table, listing the activation groups
with its properties.
In the activation group table the user can modify the input and output
state by double clicking the state and a combo box with options will be
displayed. The activation on fault, disabled and silence properties can
be checked.
To add units to the activation group, select the activation group
name in the table view and the activation group will be expand in
the tree view. See figure below.
Figure 17. AutroClient’s cause/effect view, input activation group selected.