User guide

Operating the Tool
User Guide AutroClient, Autroprime Interactive Fire Detection System, 116-P-APRIME2-AUTCLI/LGB, 2012-06-15,
Autronica Fire and Security AS
Page 15
Figure 13. Using filter and multiple select in system view to change properties on
several units.
4.4.2 Configuring Detection Zones
To configure the Detection Zones select the AutroClient toolbar DZ
button and the Detection Zones view is displayed. For a default
configuration all the detectors are connected to the Default
Detection Zone.
To add a new Detection Zone type a name and select a function.
The function options are Immediate, Dependency,Delayed
dependency, Delayed and SOLAS. The new Detection Zone will be
connected to the panel shown in the tree control (left side view).
Figure 14. AutroClient Detection Zone view.
To move detectors to the new Detection Zone, use drag and drop
in the tree view. Select the points and drag them from the Default
Detection Zone or another zone and drop them on the new
Detection Zone.
To change the Detection Zone name double click on the name and
edit, to change the Detection Zone function double click on the
function and a combo box will be displayed for selection.
The Detection Zone view has also got a filter option which is used to
filter Detection Zones or points by name, function or hardware. This
option is case-insensitive. The filter is very useful for large
configurations.