User guide
Operating the Tool
User Guide AutroClient, Autroprime Interactive Fire Detection System, 116-P-APRIME2-AUTCLI/LGB, 2012-06-15,
Autronica Fire and Security AS
Page 11
When selecting one of the user panel command buttons the
AutroClient will transmit a command message to the Autroprime
panel. The following user commands are available:
Reset: Reset alarms, remove faults etc. from the panel.
Silence: Silence Fire Alarm Devices
Resound: Resound Fire Alarm Devices
Prolong: Used on delayed Detection Zones in silent alarm to prolong
delay of activation.
Block: Used on SOLAS Detection Zones to block activation.
Activate: Used on delayed Detection Zones to start activation before
the delay has expired.
DayMode: The panel will be in day mode and delayed activation will
be enabled.
NightMode: The panel will be in night mode and immediate activation
will be enabled.
Ack Faults: All faults will be acknowledged.
4.3.2 Advanced user commands
The AutroClient’s Advanced User Commands are used for saving the
config file and restart the panel, and will often be used when
reconfiguring the panel.
The following Advanced user commands are available:
Save config: Saves the Autroprime Config.xml file.
Restart panel: Restart the Autroprime panel.
Loop power calculation: Calculation of each loop current
consumption. The loop current setting for each loop connected to the
selected panel can be set. The “Calc current consumption” displays
the loop current consumption calculated from the connected loop units
in an alarm situation. The “Validation” field indicates “FAILED” if the
Calc current consumption exceeds the “Loop current” setting.
Figure 8. Loop power calculator.
Clear log: Clear the Autroprime panel log.
4.3.3 Time and date
The AutroClient Time and Date command is used to update the time
and date at the Autroprime panel.