20. Configuration Menu
1) Edit Cons Oi Fails This option allows the operator to select the
number of consecutive Oi failures before an Oi fault will be generated.
Selectable range is 1 to 1000.
2) Edit Temp Setpoint This option allows the operator to select the
temperature at which the optics heater begins operating.
3) Edit Heater Setpoint This option allows the operator to select the
maximum amount of heater power allowed, in percent of full power.
(0% = heater shut off.)
21. Calibration Menu
1) Loop Test This test allows the operator to manually set the analog
signal output (4 to 20 mA) to a fixed user defined value.
2) D/A Trim This function allows adjustment of the 4 to 20 mA span
factor.
3) Calibrate Oi This procedure calibrates the Oi test signal for all
three IR sensors.
1. Bypass/disable all Alarm outputs connected to the detector.
2. Thoroughly clean the sensor and Oi reflector for each of the three
sensors. Check each of the three Oi source openings for
contaminants and clean as needed.
3. Cover the detector with the provided cover.
4. Initiate Oi Calibration. The detector performs the calibration
automatically and notifies the operator upon completion. The
procedure takes approximately two minutes.
5. Upon completion of Oi calibration, remove the cover and return all
alarm outputs to service.