14. Oi Menu
1) Left Oi Percentage of calibrated Oi test signal returned by the left
sensor. Reading should be 90 to 100 percent. If reading is below 90
percent, go to “Device Setup”, select “Calibration”, and perform Oi
Calibration.
2) Middle Oi Percentage of calibrated Oi test signal returned by the
middle sensor. Reading should be 90 to 100 percent. If reading is
below 90 percent, go to “Device Setup”, select “Calibration”, and
perform Oi Calibration.
3) Right Oi Percentage of calibrated Oi test signal returned by the
right sensor. Reading should be 90 to 100 percent. If reading is below
90 percent, go to “Device Setup”, select “Calibration”, and perform Oi
Calibration.
4) Oi Fail Count Number of consecutive Oi failures counted (one
passed Oi test resets the counter).
5) No. Oi Failures Set (allowable) number of consecutive Oi failures
to produce a fault.
6) Oi Cal Active Oi calibration is in progress.
7) Oi Cal Fault An Oi calibration fault has occurred.
8) Manual Oi Active A manual Oi test is in progress.
9) Manual Oi Fail The detector has failed the last manual Oi test.