13. Hardware Menu
1) Heater Power Actual heater power (0 to 100%). Heater prevents
condensation and icing on the detector optics.
2) Heater Setpoint Maximum amount of heater power allowed (in
percent of full power).
3) Temperature Actual integral temperature of detector.
4) Temp Setpoint Temperature at which heater begins operating.
5) Temp Range Fault Detector integral temperature out of range —
Operating range: –40°F to +167°F (–40°C to +75°C).
6) Voltage Actual detector supply voltage (must be 18 to 32 Vdc).
7) Volt Range Fault Supply voltage is out of range. Operating voltage
must be 18 to 32 Vdc.