Datasheet

Detector Wiring
Addendum, AutroFlame X33AF 116-P-X33AFADDENDUM/YGB, DEC P/N 95-8624, 2007-11-12, Autronica Fire and Security AS
Page 8
4. Detector Wiring
Refer to the X33AF instruction manual for complete instructions
regarding detector installation and wiring. However, note that the
device power consumption specifications for the HART model are
different than the standard model.
Power Consumption Specifications of X33AF Detector with HART
Communication
Without heater: 4.7 watts at 24 vdc nominal;
6.1 watts at 24 vdc in alarm.
5.5 watts at 32 vdc nominal;
7.4 watts at 32 vdc in alarm.
Heater only: 8 watts maximum.
Total power: 17 watts at 32 vdc with EOL resistor installed
and heater on maximum.
EOL resistor must be ceramic, wirewound type, rated 5 watts
minimum, with actual power dissipation not to exceed 1.5 watts.