User guide

Troubleshooting
System Description, AutroSafe Integrated Fire & Gas Detection System, 116-P-ASAFE-IFG/XE Rev. B, 2005-10-27,
Autronica Fire and Security AS
Page 78
To resolve fault:
1.1 - Replace faulty detector
OR
1.2 - Repair detector according to Dräger XPtox manual.
2 - Reset AutroSafe if fault is still present on panel
Dräger XPTox warning:
Fault message:
--------------------------------------------------------------
----
FAULT:
<Point Tag>
Status
Not accepted
Type:
Point -
Sensor: General warning
Reported by
<F>,<L>,<M>
--------------------------------------------------------------
----
where:
<F>: Internal data
<L>: Internal data
<M>: Internal data
To resolve fault:
1.1 - Replace faulty detector
OR
1.2 - Repair detector according to Dräger XPtox manual.
2 - Reset AutroSafe if fault is still present on panel
----------------------------------------------------------------
--------------
----------------------------------------------------------------
--------------
BSD-321 faults:
Any configuration:
Loopback fault:
Fault message:
--------------------------------------------------------------
----
FAULT:
<Loop driver tag name>
Status
Not accepted
Type:
General protocol converter -
Loopback fault detected
Data
<A>,<B>
Reported by
<F>,<L>,<M>
--------------------------------------------------------------
----
where:
<A>: Internal data
<B>: Internal data
<F>: Internal data
<L>: Internal data
<M>: Internal data
To resolve fault:
1.1 - Repair cable between channel 0 and channel 1 (ref
datasheet)
OR
1.2 - Replace broken BSD-321 unit.
2 - Reset AutroSafe if fault is still present on panel
Any configuration:
RS-485 ground fault:
Fault message:
--------------------------------------------------------------
----
FAULT: