User guide
Troubleshooting
System Description, AutroSafe Integrated Fire & Gas Detection System, 116-P-ASAFE-IFG/XE Rev. B, 2005-10-27,
Autronica Fire and Security AS
Page 77
--------------------------------------------------------------
----
FAULT:
<Point Tag>
Status
Not accepted
Type:
Point -
Sensor: Beam blocked
Reported by
<F>,<L>,<M>
--------------------------------------------------------------
----
where:
<F>: Internal data
<L>: Internal data
<M>: Internal data
To resolve fault:
1 - Remove items blocking the beam between transmitter and
receiver
2 - Reset AutroSafe if fault is still present on panel
----------------------------------------------------------------
--------------
Dräger XPtox configuration:
Faulty power wiring or
4-20mA open circuit or
faulty Dräger detector:
Fault message:
--------------------------------------------------------------
----
FAULT:
<Point Tag>
Status
Not accepted
Type:
Point -
Sensor: General fault
Reported by
<F>,<L>,<M>
--------------------------------------------------------------
----
where:
<F>: Internal data
<L>: Internal data
<M>: Internal data
To resolve fault:
1.1 - Replace faulty detector
OR
1.2 - Repair faulty wiring.
2 - Reset AutroSafe if fault is still present on panel
Dräger XPTox maintenance:
Fault message:
--------------------------------------------------------------
----
FAULT:
<Point Tag>
Status
Not accepted
Type:
Point -
Sensor: Maintenance
Reported by
<F>,<L>,<M>
--------------------------------------------------------------
----
where:
<F>: Internal data
<L>: Internal data
<M>: Internal data