User guide
Troubleshooting
System Description, AutroSafe Integrated Fire & Gas Detection System, 116-P-ASAFE-IFG/XE Rev. B, 2005-10-27,
Autronica Fire and Security AS
Page 76
--------------------------------------------------------------
----
where:
<F>: Internal data
<L>: Internal data
<M>: Internal data
To resolve fault:
1.1 - Replace detector
OR
1.2 - Clean the detector optical parts according to SimradGD10
manual.
2 - Reset AutroSafe if fault is still present on panel
----------------------------------------------------------------
--------------
Sieger Excel OPGD or Sieger Excel OPGD duct
configuration:
Faulty power wiring or
4-20mA open circuit or
faulty Sieger Excel OPGD detector:
Fault message:
--------------------------------------------------------------
----
FAULT:
<Point Tag>
Status
Not accepted
Type:
Point -
Sensor: General fault
Reported by
<F>,<L>,<M>
--------------------------------------------------------------
----
where:
<F>: Internal data
<L>: Internal data
<M>: Internal data
To resolve fault:
1.1 - Replace faulty detector
OR
1.2 - Repair faulty wiring.
2 - Reset AutroSafe if fault is still present on panel
Sieger Excel OPGD (duct) dirty optics:
Fault message:
--------------------------------------------------------------
----
FAULT:
<Point Tag>
Status
Not accepted
Type:
Point -
Sensor: Dirty optics
Reported by
<F>,<L>,<M>
--------------------------------------------------------------
----
where:
<F>: Internal data
<L>: Internal data
<M>: Internal data
To resolve fault:
1.1 - Replace detector
OR
1.2 - Clean the detector optical parts according to Sieger
excel OPGD manual.
2 - Reset AutroSafe if fault is still present on panel
Sieger Excel OPGD (duct) beam blocked:
Fault message: