User guide
Troubleshooting
System Description, AutroSafe Integrated Fire & Gas Detection System, 116-P-ASAFE-IFG/XE Rev. B, 2005-10-27,
Autronica Fire and Security AS
Page 73
Fault message:
--------------------------------------------------------------
----
FAULT:
<Loop driver Tag>
Status
Not accepted
Type:
AutroFieldBus -
Ground Fault detected
Reported by
<F>,<L>,<M>
--------------------------------------------------------------
----
where:
<F>: Internal data
<L>: Internal data
<M>: Internal data
To resolve fault:
1 - Remove ground fault
2 - Reset AutroSafe if fault is still present on panel
----------------------------------------------------------------
--------------
----------------------------------------------------------------
--------------
PowerLoop faults:
Unit removed from PowerLoop bus:
Two fault messages
Fault message 1:
--------------------------------------------------------------
----
Loop is open
between points
<Tag name point, one side of the break> (LSI)
<Tag name point, other side of the break> (LSI)
Loop and panel
<Loop driver Tag> (Loop driver
address)
<Panel Tag> (Panel switch
setting)
--------------------------------------------------------------
----
Fault message 2:
--------------------------------------------------------------
----
FAULT:
<Point Tag>
Status
Not accepted
Type:
Point -
Point not responding
Data
<A>,<B>,<C>,<D>
Reported by
<F>,<L>,<M>
--------------------------------------------------------------
----
where:
<A>: Loop driver address
<B>: Point C-adress
<C>: Internal data
<D>: Internal data
<F>: Internal data
<L>: Internal data
<M>: Internal data
To resolve fault:
1 - Disable relevant loop
2 -
2.1 - Reconnect missing unit
OR
2.2 - Replace unit if broken
3 - Enable relevant loop