User guide

Operation
7.4 Service Menu / Oil&Gas Commands
Inhibit Point
Cancel Inhibit Point
Oil & Gas Commands
Set Alarm Limits
Get Measurement Values
Inhibit Point
Cancel Inhibit Point
Oil & Gas Commands
Set Alarm Limits
Get Measurement Values
7.4.1 Inhibit Point
All loop input units can be inhibited. When one or several points are
inhibited, the point(s) will not signal alarm to outputs. An inhibited
point will however present an alarm, prealarm and early warning on all
panels and AutroCom as usual. This includes panel buzzer, panel
LEDs and panel LCD display.
It is only possible to inhibit a unit from the panel menu or via
AutroCom. An inhibited point will be inhibited until the unit is un-
inhibited, either by a manual operation or by timeout.
The procedure describes how to inhibit point(s).
System Description, AutroSafe Integrated Fire & Gas Detection System, 116-P-ASAFE-IFG/XE Rev. B, 2005-10-27,
Autronica Fire and Security AS
Page 62
Step Actions to be taken Display Indication
MENU
19:23
Total: 3
1 SHOW STATUS
2 DISABLE
3 ENABLE
4 SYSTEM
5 SERVICE
1
To enter the Main Menu, press
SERVICE
19:23
1 TEST
2 LOG
3 LOOP COMMANDS
4 OIL&GAS COMMANDS
2
To select SERVICE, press 5.