User guide

System Hardware
System Description, AutroSafe Integrated Fire & Gas Detection System, 116-P-ASAFE-IFG/XE Rev. B, 2005-10-27,
Autronica Fire and Security AS
Page 20
4.3.5 Capacity / Limitations
Each PowerLoop must be verified using the PowerLoop Calculator
(ConfigTool). Generally, the following applies:
Maximum 15 detectors can be connected to each PowerLoop.
May require forced cooling, disipates up to 30W when fully
loaded.
No branches allowed on PowerLoop or AutroFieldBus.
The total power consumption to PowerLoop units, detectors and cable
loss must be verified by the PowerLoop Calculator (part of the
AutroSafe Configuration Tool).
See also datasheet for BSD-340.