User guide
System Hardware
System Description, AutroSafe Integrated Fire & Gas Detection System, 116-P-ASAFE-IFG/XE Rev. B, 2005-10-27,
Autronica Fire and Security AS
Page 20
4.3.5 Capacity / Limitations
Each PowerLoop must be verified using the PowerLoop Calculator
(ConfigTool). Generally, the following applies:
• Maximum 15 detectors can be connected to each PowerLoop.
• May require forced cooling, disipates up to 30W when fully
loaded.
• No branches allowed on PowerLoop or AutroFieldBus.
The total power consumption to PowerLoop units, detectors and cable
loss must be verified by the PowerLoop Calculator (part of the
AutroSafe Configuration Tool).
• See also datasheet for BSD-340.