Specifications
Testing the Final Installation
8. Testing the Final Installation
When the installation is completed, verify that all BU-panels show
alarms, prealarms and faults.
When the power is turned ON, the following startup message will
appear in the BU-70 display:
S1200 01 (c)90AUT.
Program Version
Panel address 00-15
Baud rate: 1200 Baud
When communication is established, the light in the display will go off
and remain dark.
Fault messages shown in BU panel's display during startup:
If the communication between BSL-337 and the BU panels is missing,
the following text is shown:
S1200 01 (c)90AUT.e83.
The fault message (e83) means that there is no communication. The
buzzer will be activated if the communication is missing during normal
operation. The FAULT LED-indicator will also be lit.
Fault messages shown in the AutroSafe panel's display during
startup:
If the communication between AutroSafe and the BSL-337 is missing,
the following text is shown::
"Loss of communication."
If the communication between BSL-337 and BU panels is missing, the
following fault message is shown::
”Protocol converter fault.”
Note that it is important to define a name for each AutroCom port
(EAU-321/BSL-337) that is used (maximum 2 per AutroSafe panel);
for example,
“Comm. BU-panels 1-6”.
In this way, it will be easier to locate the fault.
Interfacing BU70 Display Units and BU100/BU101 Panels, AutroSafe Interactive Fire-Alarm System,
116-P-BSL337/EE, Rev. D, 2007-01-25,
Autronica Fire and Security AS
Page 31