Specifications
Configuring BSL_337
Interfacing BU70 Display Units and BU100/BU101 Panels, AutroSafe Interactive Fire-Alarm System,
116-P-BSL337/EE, Rev. D, 2007-01-25,
Autronica Fire and Security AS
Page 29
Example:
The language to be selected is English, and the total number of
BU-panels are 16.
• Set the switches according to English language (61):
BCD high: 6, BCD low: 1
• Press the reset button on the BSL-337 interface (the LED will start
flashing).
• Set the switches according to a total of 16 BU-panels:
BCD high: 1, BCD low: 3
• When the switches are set, press the reset button once more (the
LED will change to a steady light).
6.4 Standard text strings
Alarm texts are defined by means of the AutroSafe configuration tool.
These texts include detection zone information (detector names) and
consist of a maximum of 34 characters.
Alarms and operation are indicated by short language-dependent
texts on the BU-panels’ displays. Text is shown only in the event of an
alarm or prealarm. Faults are shown by the activation of a LED
indicator.
Note that in the event of an alarm or a prealarm, the same text is
shown in all BU-panels (BU-70 display units and BU-100/BU-101
panels) connected to the same AutroSafe panel (i.e. connected to the
same AutroCom port and belonging to the same operation zone).