Specifications

Configuring BSL_337
Interfacing BU70 Display Units and BU100/BU101 Panels, AutroSafe Interactive Fire-Alarm System,
116-P-BSL337/EE, Rev. D, 2007-01-25,
Autronica Fire and Security AS
Page 28
6.3 Defining language and the total number of
display units/panels
Perform the procedure in the following sequence (first define the
language, then the total number of BU-panels):
Step 1: Defining language
When defining the language, the rotary switches function as follows:
BCD high: This switch determines the number of ten-digits (6).
BCD low: This switch determines the number of one-digits (1-4).
Set the switches according to the selected language:
Language Address BCD high
ten-digits (6)
BCD low
one-digits (1-4)
English 61 6 1
Norwegian 62 6 2
Swedish 63 6 3
Danish 64 6 4
Step 2: Defining the total number of BU-panels
When the switches for the selected language are set, press the
reset button on the BSL-337 interface (the LEDs will start flashing).
When defining the total number of BU-panels, the rotary switches
function as follows:
BCD high: This switch determines the number of ten-digits (0-1).
BCD low: This switch determines the number of one-digits (0-9).
Define the total number of BU-panels.
Address BCD high
ten-digits (0-1)
BCD low
one-digits (0-9)
01 0 1
02 0 2
03 0 3
04 0 4
05 0 5
06 0 6
07 0 7
08 0 8
09 0 9
10 1 0
11 1 1
12 1 2
13 1 3
14 1 4
15 1 5
16 1 6
When the switches are set, press the reset button once more (the
LED will change to a steady light).