Specifications

Configuring BSL_337
6. Configuring BSL_337
6.1 Settings on the Panel Front
/ Language selection
= Switch in ON position
The DIP-switches and rotary switches should be set as shown in the
figure:
S1.4 ON (RS-232 on port 1)
S2.4 ON (RS-232 on port 0)
Rotary switches:
The switches are used to determine both the language (addresses 60-
64) and the the total number of BU-panels connected (addresses 01-
16).
Refer to the procedure; “Defining language and the total number of
display units/panels”, described in chapter
6.3.
6.2 Service-Computer-Based Configuration
The BSL-337 has very few configurable settings; language and port
parameter settings. Port parameter settings are modified by use of a
service computer connected to BSL-337’s service port, using a
standard AutroSafe Config Download cable (XJA-029), and then run
HyperTerminal.
Communication parameters for the service port is 115200 baud, 8
databit, no parity, 1 stop bit.
Interfacing BU70 Display Units and BU100/BU101 Panels, AutroSafe Interactive Fire-Alarm System,
116-P-BSL337/EE, Rev. D, 2007-01-25,
Autronica Fire and Security AS
Page 27