Specifications
Configuring the AutroSafe
System
• Select port number, 1 or 2.
• Verify the parameter settings (baud rate to 9 600 baud, 8 bits,
none parity, 1 stopbit).
• Set the AutroCom Type to SERIAL_SLIDING_WINDOW in the
drop-down box to the right.
• From the Main Menu, click on View and select Operation View.
• In the Tree View on the left side of the screen, click on the top level
OZ (Operation Zone) – that is, if there are several Operation Zones
in the AutroSafe system.
• Right-click the mouse and select Connect.
• In the popup menu that appears, select the Pager (in this example
we have given the Unit this name), then click on the Connect
button.
• In the Tree View, verify that the AutroCom Serial (in this example,
Pager) is connected to the correct OZ (Operation Zone).
Interfacing BU70 Display Units and BU100/BU101 Panels, AutroSafe Interactive Fire-Alarm System,
116-P-BSL337/EE, Rev. D, 2007-01-25,