3. Installation
3.1 Hardware Requirements
In order to interface BU-panels to an AutroSafe system, the following
hardware is required:
AutroSafe Serial Communication Board EAU-321 — port 1 or 2
(See section
3.7 and 3.8).
AutroSafe BU-70 Interface BSL-337
Current Loop/RS-232 Converter, BSL-12/2
Cables: XBA-055 or XGK-1/20-30 with terminal block
If more than 16 BU-panels are to be connected, additional
BSL-337 interfaces and Current Loop/RS-232 Converters
BSL-12/2 must be installed (refer to chapter
3.4).
3.2 Software Requirements
AutroSafe system software version 3.2.0 or later
AutroSafe AutroCom parameters:
- baud rate 9600
- 8 data bit
- none parity
- 1 stop bit