Specifications
Description
2.4 Indicators and buttons
/ Language selection
=
Switch in ON position
Interfacing BU70 Display Units and BU100/BU101 Panels, AutroSafe Interactive Fire-Alarm System,
116-P-BSL337/EE, Rev. D, 2007-01-25,
Autronica Fire and Security AS
Page 8
Name Color Description
PWR Green Steady ON: Power OK
Note: The LED flickers slightly once every second. This is an indication that
the software is running.
FLT Red Pulsating: Fault
The reason for the fault will normally be presented on the AutroSafe display as
a fault from BSD-337.
The Fault LED will also flash if the AutroSafe communication is lost.
ST0 Yellow Pulsating: Sending AutroSafe events to BU-panels (BU-70 and BU-100/BU-
101).
Application level indicator: The BSL-337 queues AutroSafe events , and this
LED can be lit continuously in periods with high traffic.
TX1 Green Pulsating: AutroCom data sent to AutroSafe
RX1 Red Pulsating: AutroCom data received from AutroSafe.
TX1/RX1: As a minimum, there will be communication every 3 seconds with a
brief flash in both LEDs.
TX0 Green Pulsating: data sent to BU-panels (BU-70 and BU-100/BU-101).
RX0 Red Pulsating: data received from BU-panels (BU-70 and BU-100/BU-101).
AFB TX Not in use
AFB RX Not in use
AFB ST1 Not in use
S1 DIP-switches for port 1 (to AutroSafe)
(S1.4 ON)
S2 DIP-switches for port 0 BU-panels (BU-70 and
BU-100/BU-101), (S2.4 ON)
BCD High / The rotary switches are used to determine both the language (addresses 60-
64) and the total number of BU-panels connected (addresses 01-16).
BCD Low
Refer to chapter
6.3.
BCD High
Language selection:
The switch determines the number of ten-digits (6).
Total number of BU-panels (BU-70 and BU-100/BU-101):
The switch determines the number of ten-digits (0 or 1)
BCD Low
Language selection:
This switch determines the number of one-digits (1-4).
Total number of BU-panels (BU-70 and BU-100/BU-101):
The switch determines the number of one-digits (0-9)