Instruction manual

44 2954 2370 00
QAS 30 - 45 - 60 Pd
7.3.11 IT-relay
The generator is wired for an IT network i.e. no supply lines of the
power supply are directly earthed. A failure in insulation resulting
in a too low insulation resistance, is detected by the insulation
monitoring relay.
Q1 ..... Circuit breaker for X1
Interrupts the power supply X1 when a short-circuit occurs at
the load side, or when the overcurrent protection (QAS 30:
50 A, QAS 45: 63 A, QAS 60: 100 A) is activated. When
activated, Q1 interrupts the three phases towards X1. It must be
reset manually after eliminating the problem.
X1...... Main power supply (400 V AC)
Terminals L1, L2, L3, N (= neutral) and PE (= earthing),
hidden behind the control panel door and behind a small
transparent door.
N14 ... Insulation monitoring relay
Checks the insulation resistance and activates Q1 when the
insulation resistance is too low.
S2...... Emergency stop button
Push the button to stop the generator in case of an emergency.
When the button is pressed, it must be unlocked, by turning it
anti-clockwise, before the generator can be restarted. The
emergency stop button can be secured in the locked position
with the key, to avoid unauthorized use.
7.3.12 Refinery equipment pack
This refinery equipment option consists of :
Integrated spark arrestor
Engine air inlet shut-off valve
Air inlet shut-off valve
The engine air inlet shut-off valve option will prevent over-
speeding of the engine due to combustible gases being traced
within the normal engine air intake.
The generator shall not be operated with other
networks (such as TT or TN). Doing so will cause
tripping of the insulation monitoring relay.
The generator is wired for an IT network i.e. no
supply lines of the power supply are directly
earthed. A failure in insulation resulting in too low
an insulation resistance, is detected by the insulation
monitoring relay.
At each start-up and any time a new load is
connected, the insulation resistance must be verified.
Check for the correct setting of the insulation
monitoring relay (factory set at 13 k
).
!
N14 Q1
X1
S2
X1
Q1
N14
S2