2.6.5 Remote start operation
Installation wirings:
– X25.1 & X25.2 to be wired for the remote start switch.
– X25.3 & X25.4 to be wired for the remote contactor (open/close).
2.6.6 Fail classes
All the activated alarms of the Qc1001™ have their own pre-
defined fail class.
All alarms are enabled according to one of these three statuses:
– disabled alarm, no supervision of alarm (OFF)
– enabled alarm, supervision of alarm all the time (ON)
– running alarm, only supervision when the machine is running
(RUN)
2.6.7 Event Log
The unit will keep an event log of the latest 30 events.
Events are:
– shutdowns
– service timer 1 reset
– service timer 2 reset
– unit type changes
Together with each event, the running hours at the time of the event
will be stored.
The events can only be read by means of the QcUSW.