2.6.5 Remote start operation
Installation wirings:
X25.1 & X25.2 to be wired for the remote start switch.
X25.3 & X25.4 to be wired for the remote contactor (open/close).
2.6.6 Fail classes
All the activated alarms of the Qc1001™ have their own pre-
defined fail class.
All alarms are enabled according to one of these three statuses:
disabled alarm, no supervision of alarm (OFF)
enabled alarm, supervision of alarm all the time (ON)
running alarm, only supervision when the machine is running
(RUN)
2.6.7 Event Log
The unit will keep an event log of the latest 30 events.
Events are:
shutdowns
service timer 1 reset
service timer 2 reset
unit type changes
Together with each event, the running hours at the time of the event
will be stored.
The events can only be read by means of the QcUSW.