Specifications
HE  
37 
8.2.  Switch-over from warning to shutdown function 
If a shutdown of functional elements (e.g. heater, circulating pump) is 
required when the limit values are exceeded or undercut the circulator can 
be changed over from warning function >WARNING< to shutdown function 
>ALARM<. 
Factory setting: 
>WARNING< 
1.  Press the key 
. 
2.  Select the menu >SECVAL -AL-TYPE< by pressing the 
 key. 
3.  Press the 
 key and the set parameter will flash  . 
(Example: WARNING)  
4.  Change the parameter by pressing the 
 key and confirm by 
pressing the 
 key. 
or 
press the 
 key if the parameter is to retained.  
 Setting >WARNING< 
A mere warning function with optical and audible warning signal (interval 
tone) A message appears on the VFD COMFORT-DISPLAY: 
 or   
OVERTMP    SUBTEMP 
•  Setting >ALARM< 
Temperature limit with shutdown of heater and circulating pump. 
An audible alarm sounds (continuous tone) and a message appears on 
the VFD COMFORT-DISPLAY: 
 or   
OVERTMP    SUBTEMP 