Specifications

RSLinx – Training Guide 19
Application Notes and Suggestions (continued)
When receiving unsolicited messages from an SLC 500 processor via a 1785-
KA5 Bridge, the DDE topic's remote configuration must be set to Internet mode.
Ø Also, in the SLC 500 message instruction, the remote bridge node
address must be set to 0.
Ø Also, unsolicited messages sent from a PLC or other node to RSLinx will
cause errors if no DDE clients or C-API applications are running to
receive them.
When downloading a program to an SLC 500, stop all data connections active to
that station. Under certain instances, the processor may fault if applications
continue to poll the SLC during a download.
If you are running Windows 95 using the 1747-PIC driver with WINtelligent LINX,
but are no longer using WINtelligent LINX, we recommend you change the
following entry in your system.ini file (located in \Windows directory). Under the
[boot] section of the system.ini file, change comm.drv = icomcomm.drv to
comm.drv = comm.drv After changing this entry, restart Windows 95.
RSLinx does not automatically create a NetDDE share entry in the NT or
Windows 95 registry for configured topics. For help on enabling NetDDE and
creating NetDDE shares, refer to the NetDDE help page.
RSLinx will not reread a User Defined Structure list for SoftLogix until the topic is
stopped and restarted.
RSLinx supports no-interrupt configurations when using Allen-Bradley network
cards; however, we recommend assigning an interrupt to increase driver
performance.
If you have Auto Hide on for the Windows task bar, every time you go to the task
bar (if animation is on), it reduces your packets/sec speed due to computation
times.
Do not use the power saver option on your computer when running RSLinx. Use
either the BIOS or Control Panel to disable this option.