Configuring Your ASCII Module 2-25
A transmission of the serial data from the ASCII module to your ASCII 
device can be initiated in two ways. If an I/O connection is used, 
serial data in the mapped I/O location will be sent to the ASCII 
module on every I/O command (repeatedly at the same interval of the 
DeviceNet scanner).
· In Transmit Handshake Mode, changing the transaction ID will 
always initiate a transmission on the network. Even if you do not 
set new data into the data string, the old data will be 
transmitted.
· In Transmit Immediate Mode, the ASCII module will transmit 
data out its serial port every time it receives an I/O command or 
explicit message to its transmit buffer or changes the transaction 
ID.
ATTENTION
!
An I/O message is repeatedly sent and generates 
internal writes to Class 71, Instance 1, attribute 3. 
This will cause you to send large amounts of data to 
your device and can cause TX Buffer Overflows. You 
may experience corrupted data and improper 
information sent to your serial device when using 
data only mode with I/O messaging.
ATTENTION
!
You should take care when activating Transmit 
Immediate mode while I/O Polling is active. In this 
mode of operation, the module will continuously 
transmit serial data to the target serial device. If the 
data string represents a command message to your 
target device, these actions could result in 
unintended misoperationg of your device or system.