Configuring Your ASCII Module 2-19
Setting Up the Scanner I/O Receive Size
The ASCII modules automatically calculate the number of bytes it will 
send to the DeviceNet master. Its value is determined by a 
combination of the incoming data and the options you have selected. 
Parameter 13 defines the size of the DeviceNet message to be sent by 
the ASCII module to the master.
Table 2.4 Receive Data Format - Array Data Type
Byte 1 Byte 2 Byte 3 Byte 4 Byte 5-X Byte X+1
(Max = 132)
RX Transaction ID 
Byte
Status Byte Reserved Reserved ASCII Data 
(max 128 bytes)
<CR>
(Terminator)
Table 2.5 Receive Data Format - Short_String Data Type
Byte 1 Byte 2 Byte 3 Byte 4 Byte 5-X Byte X+1
(Max = 132)
RX Transaction ID 
Byte
Status Byte Reserved Length ASCII Data 
(max 128 bytes)
<CR>
(Terminator)
Table 2.6 Receive Data Format - String Data Type
Byte 1 Byte 2 Byte 3 Byte 4 Byte 5-X Byte X+1
(Max = 132)
RX Transaction ID 
Byte
Status Byte Length (Low Byte) Length (High Byte) ASCII Data 
(max 128 bytes)
<CR>
(Terminator)
IMPORTANT
You must set your scanner’s RX (receive) value to 
this number of bytes.
IMPORTANT
You must upload this data from the ASCII module to 
view current information or put your RSNetWorx for 
DeviceNet into Monitor Mode.