User manual
SETTINGS
24 July 2012 / WPC / EN
- --
1222
Start hour (AUX 1)
07:00
hh:mm
1223
End hour (AUX 1)
20:00
hh:mm
Important: the period cannot be set over midnight. If the required silent time is e.g. from 22.00pm till
7.00am, then two periods have to be programmed.
Period 1 start hour: 22.00, end hour: 24.00
Period 2 start hour: 00.00, end hour: 7.00
It is also possible to automatically start on fixed intervals instead of upon load or battery demand.
This is however not typical for the GV-7i installation. Refer to manual for details.
8.6 USER PREFERENCE: DIPSWITCH FUNCTIONS
To set the behavior of the input switching component of the WPC a dipswitch is available at the
input switching board. To access it, open the connection compartment cover. The figure below
show the location of the dipswitch.
Figuur 10 – Dipswitch location
Dipswitch
Function
Default
1
Prohibit automatic start when grid is available
Off
2
Preferred input ON = Generator
Off = Grid
On
8.6.1
Prohibit automatic start when grid is available
Default the generator will automatically start when one of auto start criteria is met. It starts even
when the is AC grid is connected. In some cases the AC grid can supply more power than the
generator. In this situation it is most likely that starting of the generator is not wanted. To prohibit the
generator from starting in this situation set the upper dipswitch to the “ON” position. Now the
Autostart signal will indicate “start” only when there is no grid available. Refer to the figure above
for the position of the dipswitch.