User manual
SETTINGS
July 2012 / WPC / EN 23
1261
Inverter power level 2 activate (AUX 1)
Yes
No/Yes
1262
Power level 2 (AUX 1)
100
% Pnom
1263
Time delay 2 (AUX 1)
5
min
1264
Inverter power level 3 activate (AUX 1)
Yes
No/Yes
1265
Power level 3 (AUX 1)
110
% Pnom
1266
Time delay 3 (AUX 1)
1
min
To deactive:
Contact active with inverter power or Smart-Boost (AUX 1)
Default
1267
Inverter power level to deactivate (AUX 1)
40
% Pnom
1268
Time delay to deactivate (AUX 1)
5
min
8.5 ENABLE A SILENT PERIOD
To prevent the generator from automatically starting within a specified period (e.g. at night), it is
possible to set a silent period. Setting a silent period is done using the program parameters of the
AUX 1 signal. Below are the parameters listed, in total you can set 5 different programs.
1203
Temporal restrictions (AUX 1)
default
1204
Program 1 (AUX 1)
1205
Day of the week (AUX 1)
-- -- -- -- -- -
- --
Days
1206
Start hour (AUX 1)
07:00
hh:mm
1207
End hour (AUX 1)
20:00
hh:mm
1208
Program 2 (AUX 1)
1209
Day of the week (AUX 1)
-- -- -- -- -- -
- --
Days
1210
Start hour (AUX 1)
07:00
hh:mm
1211
End hour (AUX 1)
20:00
hh:mm
1212
Program 3 (AUX 1)
1213
Day of the week (AUX 1)
-- -- -- -- -- -
- --
Days
1214
Start hour (AUX 1)
07:00
hh:mm
1215
End hour (AUX 1)
20:00
hh:mm
1216
Program 4 (AUX 1)
1217
Day of the week (AUX 1)
-- -- -- -- -- -
- --
Days
1218
Start hour (AUX 1)
07:00
hh:mm
1219
End hour (AUX 1)
20:00
hh:mm
1220
Program 5 (AUX 1)
1221
Day of the week (AUX 1)
-- -- -- -- -- -
Days