User manual

SETTINGS
July 2012 / WPC / EN 11
AGM
55Ah
80Ah
100Ah
145Ah
200Ah
260Ah
Parameter
1138*
16.5A
24.0A
30.0A
44.0A
60.0A
78.0A
1159
4A
4A
10A
10A
10A
10A
Table 2 AGM battery settings according to capacity
GEL
100Ah
145Ah
180Ah
225Ah
Parameter
1138*
20.0A
29.0A
36.0A
45.0A
1159
4A
6A
10A
10A
Table 3 - GEL battery settings according to capacity
Traction
600Ah
800Ah
1000Ah
1200Ah
1500Ah
Parameter
1138*
240A
320A
400A
480A
600A
1159
10A
10A
10A
10A
10A
Table 4 - Traction battery settings according to capacity
* Note: the maximum setting of parameter 1138 will be equal to the maximum of the battery
charge current which the specific WPC model can provide.
6.2 BATTERY TEMPERATURE SENSOR (BTS)
The temperature sensor is available as option. It must be connected to the BTS input on the WPC.
The following setting is relevant when using a BTS.
Parameter
Name
Default
1139
Battery temperature compensation
-4
mV/°C/cell
6.3 BATTERY STATUS INDICATOR (BSI)
When the BSI is connected, the state of the battery is not monitored by voltage only. The BSI
estimates the actual capacity of the connected battery and the state of charge by measuring the
current with the installed shunt. If the BSI is connected, it is also possible to automatically start and
stop the generator according to the state of charge. Refer to the auto start paragraph for the BSI
settings
Installation of the BSI is described in its own manual.