6 BATTERY SETTINGS
6.1 DEFAULT BATTERY SETTINGS
Different battery types require different settings which indicate if the battery is full or empty, for
protection values, for charge regulation and auto start/stop criteria. In the following table the
parameters are listed which are relevant when installing a battery set (multiply the value by 2 or 4,
for 24V and 48V sets):
Parame
ter
AGM
(default)
GEL
Traction
2V 6x
1138
Battery charge current
Refer to
Table 2
Refer to
Table 2
Refer to
Table 4
Adc
1139
Battery temperature compensation
-4
-4
-4
mV/°C/
cell
1108
Battery undervoltage level without load
11.6
11.6
11.6
Vdc
1109
Battery undervoltage level at full load
10.5
10.5
10.5
Vdc
1190
Battery undervoltage duration before turn off
3
3
3
min
1110
Restart voltage after batteries undervoltage
12
12
12
Vdc
1196
Battery low level for acoustic alarm
10.8
10.8
10.8
Vdc
1195
Max voltage for adaptive low voltage
12.5
12.5
12.5
Vdc
1307
Reset voltage for adaptive correction
13.2
13.2
13.2
Vdc
1298
Increment step of the adaptive low voltage
0.1
0.1
0.1
Vdc
1121
Battery overvoltage level
17
17
17
Vdc
1122
Restart voltage level after an battery overvoltage
16.2
16.2
16.2
Vdc
1140
Battery floating level
13.6
13.6
13.5
Vdc
1143
Battery voltage level 1 to start a new cycle
12.5
12.5
12.5
Vdc
1144
Time period under battery voltage level 1 to start a new cycle
30
30
30
min
1145
Battery voltage level 2 to start a new cycle
12.3
12.3
12.3
Vdc
1146
Time period under battery voltage level 2 to start a new cycle
60
60
60
sec
1149
New cycle priority on absorption and equalization phases
No
No
No
No/Yes
1155
Absorption phase allowed
Yes
Yes
Yes
No/Yes
1156
Battery absorption voltage
14.4
14.4
14.1
Vdc
1157
Absorption duration
2
2
2
hours
1158
End of absorption triggered with current
Yes
Yes
Yes
No/Yes
1159
Current limit to quit the absorption phase
Refer to
Table 2
Refer to
Table 3
Refer to
Table 4
Adc
Table 1 Battery settings