Service manual
Operating Procedures
Illustration
(4) Remove the 4-way valve
and capillary
1. Remove the 4-way valve
● Loosen the screws fixing the
electromagnetic coil on the 4-way
valve.
● Remove the electromagnetic coil.
● Cut the weld between the 4-way
valve and other pipes.
● Remove the 4-way valve. (See Fig.
10)
Note: When cutting the weld, take
care to prevent the flame from
touching other parts. The valve body
shall be completely wrapped with wet
cloth in order to avoid damage under
high temperature.
2. Remove the capillary
● Cut the two welds between capillary
and other pipes.
● Remove the capillary. (See Fig. 11)
Electromagnetic coil
Fig.10
Fig.11
60