The right temperature worldwide Operating instructions Variocool VC 600, VC 1200 (W), VC 2000 (W), VC 3000 (W), VC 5000 (W), VC 7000 (W), VC 10000 (W) Circulation chiller
LAUDA DR. R. WOBSER GMBH & CO. KG Postfach 1251 97922 Lauda-Königshofen Germany Phone: +49 (0)9343 503-0 Fax: +49 (0)9343 503-222 E-Mail: info@lauda.de Internet: www.lauda.
Table of contents Table of contents 1 Safety.................................................................................................................................................... 7 1.1 General safety instructions.......................................................................................................... 7 1.2 Intended use................................................................................................................................ 8 1.3 Foreseeable misuse.
Table of contents 4.4.2 4.5 5 Interfaces................................................................................................................................... 29 4.5.1 Alarm output 12N....................................................................................................... 29 4.5.2 Installing driver for USB interface............................................................................... 30 4.5.3 Connecting device to a PC.............................................
Table of contents 6.11.3 Setting display brightness.......................................................................................... 55 6.11.4 Specifying starting mode (Autostart).......................................................................... 55 6.11.5 Limiting current consumption..................................................................................... 56 6.11.6 Configuring alarm level for fill level.....................................................................
Table of contents 10 9.1 Draining device.......................................................................................................................... 79 9.2 Draining condenser (only water-cooled devices)...................................................................... 80 Disposal.............................................................................................................................................. 81 10.1 Disposing of refrigerant.................................
Safety 1 Safety 1.1 General safety instructions The devices must only be operated for the intended use under the conditions stated in this operating manual. Any other type of operation is considered to be non-intended use and can impair the protection provided by the device. The operating manual is part of the device. The information in this operating manual must therefore be available in the immediate vicinity of the device. Also keep this copy of the operating manual carefully.
Safety 1.2 Intended use Intended use The present device is exclusively permitted to be used for tempering and delivering non-combustible heat transfer liquids in a closed circuit. Non-intended use The following applications are considered to be not-intended: medical applications in potentially explosive areas for tempering foodstuffs with a glass reactor without overpressure protection 1.3 Foreseeable misuse Misuse of the device must be prevented in any case.
Safety In each case, the heat transfer liquids cover a specific temperature range. This temperature range must match the temperature range of your application. The use of heat transfer liquids can cause hazards from high or low temperatures and fire if certain temperature thresholds are exceeded or undercut or if the container breaks and there is a reaction with the heat transfer liquid .
Safety 1.9 Personnel qualification Operating personnel Operating personnel are personnel who have been instructed by specialist personnel about the intended use of the device according to the operating manual. Specialist Specific activities on the device must be carried out by technical staff. Technical staff is personnel that can evaluate functions and risks of the device and the application based on their training, skills and experience. 1.
Safety 1.12 Danger Structure of the safety instructions A safety instruction of the type "Danger" indicates an immediately hazardous situation. This results in death or severe, irreversible injuries if the safety instruction is disregarded. DANGER! Type and source Consequences in the case of non-compliance Measure 1 Measure… Warning A safety instruction of the type "Warning" indicates a potentially hazardous situation.
Safety Notice A "notice" warns about possible property or environmental damage.
Unpacking 2 Unpacking DANGER! Transport damage Electric shock Inspect the device for transport damage before commissioning. Never put the device into operation if you have discovered any transport damage. Personnel: 1. Operating personnel Unpack the device. Keep the original packaging of your device for later transport. 2. Inspect the device and the accessories immediately after delivery for completeness and transport damage.
Design and function 3 Design and function 3.1 Device types The type designation of the devices is composed of the following integral parts. Element Description VC Variocool , e.g. 5000 Specification of the cooling capacity in watts [W] at 20 °C W Device with water cooling This specification in the device type is optional. It identifies water-cooled devices. All devices are intended as floor-standing units. The devices have castors with locking brakes.
Design and function 3.2 Design of the device Fig.
Design and function Fig. 2: Rear side VC 5000 W 1 2 3 4 5 6 7 8 9 10 Pump connection, outlet Bypass adjusting wheel (starting with VC 1200 (W)) Pump connection, return Drain tap Water cooling outlet (only for water-cooled devices) Water cooling inlet (only for water-cooled devices) Ventilation grille Rating plate Mains cable Fuses (up to and including VC 3000 (W)) Control panel Fig.
Design and function 3.3 Controls 3.3.1 Mains power switch VC 600 to VC 3000 (W) The mains power switch can be toggled between the following positions: In position [I], the device is switched on. In position [O], the device is switched off. VC 5000 (W) and higher The mains power switch can be turned to the following positions: In position [I], the device is switched on. In position [O], the device is switched off. 3.3.
Design and function Detailed information about the technical data of the pump can be found in Ä Chapter 11.3 ‘Standard and optional pumps’ on page 85. 3.4.2 Manometer The device types with bypass have a manometer for reading the pump pressure which can be regulated via the bypass of the machines. The bypass is available for device types starting with model VC 1200 (W). Fig. 5: Manometer 3.4.
Design and function Note the following: The equipment connected to the low voltage inputs and outputs must have safe separation from dangerous voltages according to DIN EN 61140 such as by double or reinforced insulation according to DIN EN 60730-1 or DIN 60950-1. USB interface The devices are equipped with a USB interface (type B) as standard. This enables, for example, connection to a PC and operation using the Wintherm Plus control software.
Design and function Detailed information for the connection and use of these interfaces can be found in the operating manual of the respective LAUDA interface module. 3.5 Options The options installed in the device can be recognised on a sticker underneath the rating plate. Heater A heater is possible as an option for all devices. This option is only possible at the factory. More powerful pump For these options, reinforced pumps are installed starting from the VC 1200 (W) devices.
Design and function Sound insulation Sound insulation is possible as an option for theVC 5000 (W), VC 7000 (W) and VC 10000 (W) devices. This option is only possible at the factory. Cooling water insulation Cooling water insulation is possible as an option for the VC 1200 W to VC 10000 W devices. This option is only possible at the factory. 3.6 Rating plate The rating plate specifications are explained in detail in the following table. Certain specifications are dependent on installed device options.
Design and function Specification Description Fuse optional heater fuse used in the device; only applicable for devices with optional heater Class according to DIN 12876-1 Device class according to DIN 12876-1 3.7 Serial number The serial number of a LAUDA device has the following structure: LAUDA catalogue number Year of manufacture The year is indicated with two digits. Sequential number of the device in the year of manufacture. The sequential number is a four-digit number.
Before commissioning 4 Before commissioning 4.1 EMC classification Approval of the devices according to EMC classification Countries EMC class Europe Class B This classification has been made according to the EMC standard DIN EN 61326-1 (corresponds to VDE 0843-20-1). USA Class A This classification has been made according to the FCC (Federal Communications Commission) regulations, Section 15.
Before commissioning Instructions for Class A digital device, Canada “This Class A digital apparatus complies with Canadian ICES-003” (ICES = Interference Causing Equipment Standards)". « Cet appareil numérique de la classe A est conforme à la norme NMB-003 du Canada ». 4.2 Placement Very specific placement conditions are applicable for the devices. These placement conditions are mainly specified in the technical data of the device.
Before commissioning 2. Lock the castors of the device. Press the lever downward to lock them. 3. Attach the "Hot surface" warning sticker in a clearly visible position for applications above 70 °C. 4.3 External consumer 4.3.1 Temperature control tubes and hose clamps CAUTION! Discharge of heat transfer liquid during operation caused by use of unsuitable tubes Scalding, frostbite Use tubes with temperature resistance that is appropriate for the operating temperature range of the device.
Before commissioning Device Type Pump connection VC 600 EPDM tube, not insulated M16 x 1 (10), olive 13 mm VC 600 EPDM tube with fabric reinforcement EPDM tube with fabric reinforcement EPDM tube with fabric reinforcement M16 x 1 (10), olive 13 mm VC 1200 to VC 5000 (W) G ¾ (15), olive ¾" VC 7000 to VC 10000 (W) G 1¼ (20), olive 1" Required accessories Maximum operating pressure Clear width x outer diameter in mm Temperature range in °C Catalogue number Olive HKO 026, union nut HKM 032 < 1 bar
Before commissioning Note the following: Temperature control tubes: Always use the largest possible diameters and shortest possible tube lengths in the external circuit. If the temperature control tube diameter is too small, a temperature drop between device and external consumer occurs due to flow rate too low. In this case, increase or lower the temperature accordingly. Secure the temperature control tubes with hose clamps.
Before commissioning Data Value Unit Hydrogen carbonate [HCO3-] / Sulphates [SO4 2-] Water hardness (alkaline earth ions content) > 1.0 0.71 - 1.52 mmol/L Hydrogen carbonate [HCO3-] 70 – 300 mg/L Conductivity 10 - 500 μs/cm < 50 mg/L Chlorides (Cl-) Sulphite (SO3 2-) < 1 mg/L Free chlorine gas (Cl2) < 1 mg/L < 100 mg/L Nitrates (NO3 -) Ammonia (NH3) < 2 mg/L Iron (Fe), dissolved < 0.2 mg/L Manganese (Mn), dissolved < 0.1 mg/L Aluminium (Al), dissolved < 0.
Before commissioning Prevent kinking or squeezing of the tubes. We recommend using a leak detector with water shut-off to prevent damage due to cooling water system leaks. Ensure that the cooling water meets the required criteria. In the case of leaks in the condenser, there is the danger that refrigerator oil and refrigerant from the refrigerant circuit of the device can get into the cooling water.
Before commissioning Note the following: The equipment connected to the low voltage inputs and outputs must have safe separation from dangerous voltages according to DIN EN 61140 such as by double or reinforced insulation according to DIN EN 60730-1 or DIN 60950-1. Only use shielded connection cables; connect the shield to the connector cases. Cover unused plug connections with protective caps. 4.5.
Before commissioning Establishing connection Personnel: Operating personnel 1. The device and the PC are switched on. 2. Connect the device and the PC using a USB cable. The USB cable is not included in the scope of delivery. Windows XP: During the first start-up, the wizard for searching for new hardware opens. 3. Follow the instructions of the wizard on your PC. The software for the new device is installed.
Before commissioning 1. Touch the grounded, bare metal stainless steel rear side of the circulation chiller to discharge any electrostatic charge. 2. Remove the module from the packaging. 3. Switch off the circulation chiller and unplug the mains plug. 4. The module slots are protected with a cover. Undo the screws of the cover for the appropriate module slot and remove the cover carefully. 5. Carefully detach the bus connection cable from the cover. 6.
Commissioning 5 Commissioning 5.1 LAUDA heat transfer liquids Note the following: The heat transfer liquids each cover a recommended temperature range and must be suitable for the temperature range of your application. At the lower limit of the temperature range, the heat transfer liquid becomes more viscous and influences temperature constancy, pump power and cooling capacity. The formation of vapours and odours increases in the upper range.
Commissioning The water must be free of impurities. Water containing iron is unsuitable due to rust formation and untreated river water is unsuitable due to algae formation. The addition of ammonia is not permitted. Use of DM water The use of demineralised (DM) water is optionally possible for the devices VC 600, VC 1200 (W) and VC 2000 (W). This option is only possible at the factory. 5.
Commissioning To fill an external consumer, press the Standby softkey when there is sufficient fill level to start the pump. The heat transfer liquid now pumped into the external consumer can be refilled immediately. If the fill level drops too far, the device automatically goes into the standby operating mode and the pump is switched off. This process is performed until the device and the connected consumer are filled.
Commissioning WARNING! Spraying of heat transfer liquid Electric shock Avoid spraying heat transfer liquid. Use a funnel for filling. 1. Close the drain tap. Turn the lever to the left for this. 2. Switch on the device using the mains power switch. For VC 600 to VC 3000 (W), press the mains power switch to the position [1]. For VC 5000 (W) and higher, turn the mains power switch to the position [1]. A signal tone sounds.
Commissioning 5. Fill the device with heat transfer liquid. In doing so, monitor the display on the screen and the audible signal of the device. If necessary, use a funnel for the filling. 6. Close the filler nozzle with the cover. 7. End the fill mode by selecting and confirming End filling . After ending the fill mode, the device starts the temperature control provided the start operating mode is not set to off . Fig. 10: Fill mode Changing the start operating mode can be found in Ä Chapter 6.11.
Commissioning Personnel: Operating personnel CAUTION! Bursting of the external consumer Scalding, frostbite, impact, cutting A bypass regulator is provided to set the pump pressure (starting from VC 1200). For consumers with a maximum permissible operating pressure below the maximum pressure of the pump, use a safety valve for protection. This safety valve must be installed in the flow of the device. 1.
Operation 6 Operation 6.1 General safety instructions CAUTION! Overheating beyond maximum operation temperature in the event of a fault Burns, scalding In the event of a fault, temperatures can reach up to 100 °C with the heater option. 6.2 Operating modes Two operating modes are supported for the devices. During operation, the components of the device are operated. In the standby operating mode, all components of the device are switched off. Only the screen of the device is supplied with power.
Operation Fig.
Operation Menu structure for Graph, Clock and Standby Fig.
Operation 6.4 Switching on the device Personnel: 1. Operating personnel Switch on the device using the mains power switch. A signal tone sounds. Further information about switching on can be found in Ä Chapter 5.3.2 ‘Switching on and filling device’ on page 35. 2. The basic window is displayed. After switching on, the device defaults to the standby operating mode if the start operating mode is not set to on . Changing the start operating mode can be found in Ä Chapter 6.11.
Operation 1 2 External actual temperature Text (depending on set control variable, the internal actual temperature Tint is also displayed here) Setpoint value Tset 1 2 3 Softkey button, left Menu button Softkey button, right Fig. 17: Status display The functions of the softkeys and the function of the Menu button are shown in this bar. Fig.
Operation 6.5.2 Menu window Navigating to the main menu 1. You can perform the following steps to reach the main menu: Press the ENTER button in the basic window. If you are in a submenu, you can return to the main menu with the left arrow button. Main menu structure The main menu and also the submenus consist of menu items which are marked as follows. Symbol Description Indicates that other menu levels (submenus) are available. The padlock symbolises a blocked function.
Operation Navigation in the menus 1. You have the following options: Use the UP and DOWN arrow buttons to navigate between the menu items. Press the RIGHT arrow button to select a submenu. Press the LEFT arrow button to return to a previous menu. The selected menu entry is highlighted in colour. 6.5.3 Input window The input window is used for configuration of settings on the screen. There are different versions of input windows.
Operation Personnel: Operating personnel 1. Change to the main menu. 2. Select the menu item Setup Temp. limits. 3. Select one of the following options: Select the first entry Til to set the lower limit value. Select the second entry Tih to set the upper limit value. Fig. 25: Selecting temperature limit value 4. Adjust the value in the following input window. Fig. 26: Defining temperature limit value 6.7 Specifying setpoint value Personnel: Operating personnel 1.
Operation Personnel: 1. Operating personnel Press the [Standby] softkey button. The device is in the standby operating mode. The Standby entry in the softkey bar is highlighted. This operating mode is also shown in the expanded status display. 2. Press the Standby softkey button to activate the Operation operating mode. Fig. 28: Basic window in Standby 6.9 External control 6.9.1 Activating external control Personnel: 1.
Operation Navigating to the settings Personnel: Operating personnel 1. Change to the main menu. 2. Select the menu item Setup Control Setpoint offset. 3. Select one of the following options: With Offset source , you can specify which source to use to measure the offset. With Diff. set/actual value , you can specify the offset. Fig. 30: Setpoint offset menu Specifying offset source Personnel: Operating personnel 1. Select the menu item Offset source in the Setpoint offset menu. 2.
Operation 6.10 Control The internal and external control parameters are preset at the factory for operation as circulation chiller (with water as heat transfer liquid). Depending on the application, adjustments of the control parameters can be necessary from case to case. The thermal capacity and the viscosity of the heat transfer liquid also influence the control behaviour and may require adjustment of the control parameters. 6.10.
Operation Other precautions The viscosity of the heat transfer liquid changes very strongly with the temperature. The liquids have higher viscosity at low temperatures. Therefore, the control quality is generally worse at low temperatures. For this reason, the controller should be set at the lower end of the temperature range to be covered. If the control is stable at low temperatures, then it is generally also stable at high temperatures.
Operation If the proportional range is selected too small, the P part on the control value is at 100 % for a very long time. This value then reduces more quickly within the proportional range, i.e. the control value reduces rapidly and the approach of the actual value to the setpoint almost comes to a standstill. Due to the I part not becoming effective until now, the actual value approaches the setpoint slowly. Fig.
Operation 6.10.3 Overview of internal control parameters The internal control compares the setpoint value with the outlet temperature and calculates the control value, i.e. the amount to be heated or cooled. The following control parameters can be adjusted for the internal control: Parameter Description Unit Xp Proportional range K Tn Reset time s Tv Lead time s Td Damping time s If Tv manual/auto is set to auto , Tv and Td cannot be changed.
Operation 3. Confirm with the OK button. Selection of the menu item Tv manual/auto activates manual or automatic adjustment of the parameters depending on the previous setting. An input window is displayed when the other menu items are selected. The respective value can be adjusted within the displayed limits. 4. Adjust the value accordingly. 5. Confirm with the OK button. Fig. 39: Specifying internal control parameters 6.10.
Operation The temperature limits Tih and Til also influence the control. 6.10.6 Adjusting external control parameters Personnel: Operating personnel 1. Select the menu item Control Parameter extern Pt100 in the Control menu. 2. Select one of the following options: You can select any of the listed control parameters. With Tv manual/auto , you can define whether the control parameters Tve , Tde and Prop_E are set manually or automatically.
Operation Personnel: Operating personnel 1. Change to the main menu. 2. Select the menu item Setup Basic setup Sounds. 3. Select one of the options depending on which sound you want to adjust. 4. Select a volume level. 5. Confirm with the OK button. Fig. 41: Setting volume 6.11.3 Setting display brightness The devices have a sensor which automatically adjusts the display brightness according to the ambient light level. Adjustments to this setting are usually not necessary.
Operation Personnel: Operating personnel 1. Change to the main menu. 2. Select the menu item Setup Basic setup Autostart. 3. Select one of the following options: With off , the device is in the standby operating mode after a mains power failure. Normal operation is continued directly after a power failure using on . 4. Confirm with the OK button. Fig. 43: Specifying Autostart 6.11.
Operation 6.11.6 Configuring alarm level for fill level A warning about low level of the device is usually output on the device starting from the second level stage. However, the alarm level before low level can be configured within a specific range. Personnel: Operating personnel 1. Change to the main menu. 2. Select the menu item Setup Basic setup Warn level niveau. 3. You can select from four stages 0 to 3 for the warning before "low level".
Operation Personnel: Operating personnel 1. Change to the main menu. 2. Select the menu item Setup Basic setup Language. 3. Select any of the available languages. 4. Confirm with the OK button. Fig. 47: Selecting menu language 6.12 Entering the offset of the internal actual temperature (calibration) Deviations from calibrated reference thermometers such as LAUDA DigiCal can be corrected internally using the "Offset" function. Personnel: Operating personnel 1. Change to the main menu.
Operation Fig. 49: Factory calibration setting 2. Select the menu item Setup Calibration Factory Calibration. 3. Select one of the following options: Selecting no returns to the previous display without making any changes. Selecting yes restores the factory calibration. Fig. 50: Restoring factory calibration 6.14 Restoring factory settings Navigating to the factory settings Restoring individual settings Personnel: Operating personnel 1. Change to the main menu. 2.
Operation 3. Select one of the following options in the input window: Selecting no returns to the previous display without making any changes. Selecting yes resets the selected parameter if you confirm this with the OK button. Restoring all settings Personnel: Operating personnel 1. Select the menu item Reset all . 2. Select one of the following options: Selecting no returns to the previous display without making any changes.
Operation 2. You can navigate through the list using the UP and DOWN arrow buttons. The following information is displayed for each message: The relevant module which causes the message is displayed under Source . Code is the coded alarm, warning or error description. Type specifies alarm, warning or error. The exact time of the message is displayed with Date and Time A list of the possible alarms, warnings and errors can be found in Ä ‘Procedure in the event of alarms’ on page 74. Fig.
Operation 6.15.5 Displaying device type The device type is shown directly at the menu item Type in the Device Status menu. 6.15.6 Displaying serial numbers Personnel: 1. Operating personnel Select the menu item Serial numbers in the Device Status menu. The serial number of the device is displayed. The serial numbers of connected modules are also displayed if they are available. Fig. 58: Serial numbers 6.16 6.16.
Operation Setting Description Tolerance Tolerance defines the level of accuracy with which the end temperature should be reached before the next segment will be processed. S1, S2, S3 Switching contacts of the contact module (if available) can be programmed here. Contact modules are available as accessories. The graph shows an example of reprogramming a setpoint temperature profile. Fig. 59: Program example The cooling time in the graph varies depending on device type, consumer etc.
Operation afterwards (- - - -, edited) No. Tend hh mm Tol Pum p S1 S2 S3 Start 30.00 -- -- 0.1 --- off off off 2 50.00 0 20 0.0 --- off off off 3 50.00 0 20 0.1 --- off off off 4 70.00 0 20 0.0 --- off off off 5 70.00 0 10 0.8 --- off off off 6 60.00 0 30 0.0 --- off off off 7 30.00 0 0 0.0 --- off off off The entered tolerance can have a great influence for external bath control.
Operation The tolerance field enables precise adherence to the delay time at a specific temperature. Only after the actual temperature of the tolerance range has been reached (1), will the following segment be processed so that e.g. the ramp of the second segment will not be started until after a delay of 2. A tolerance range that has been selected too narrow can also cause undesired delays. Particularly for external control, the range should not be too narrow.
Operation Personnel: Operating personnel 1. Select the menu item Edit for the selected program. 2. You can now edit the segments. Fig. 62: Editing program Editing segments Personnel: Operating personnel Note the following: No time specification is possible in the starting segment. The temperature of the first segment is reached as quickly as possible to change to segment 2 after reaching the set tolerance.
Operation Inserting a new segment Personnel: Operating personnel 1. Navigate to the segment below which the new segment should be inserted. 2. Navigate to the No. column in this segment. 3. Press ENTER. A new segment is created. Fig. 63: Selecting program segments Deleting a segment Personnel: Operating personnel 1. Navigate to the segment you want to delete. 2. Navigate to the No. column in this segment. 3. Press the Delete softkey button. The segment is deleted.
Operation 2. The currently running program opens. 3. You can now edit the segments of the currently running program. Fig. 64: running program Completing editing Personnel: 1. 6.16.4 Operating personnel When you have completed the program, you can return to the program overview with the LEFT arrow button. Defining program loops Personnel: 1. Operating personnel Select the Loops menu item for the selected program. An input window is displayed.
Operation 6.16.5 Starting, interrupting and ending a program Personnel: Operating personnel 1. Select the Status menu item for the selected program. 2. You have the following options: Fig. 67: Setting program status Select the Start option to start the program. If the program is started, it can be interrupted using Pause . An interrupted program can be continued using Continue . Select the Stop option to end the program. Fig.
Maintenance 7 Maintenance 7.1 General safety instructions DANGER! Contact with live or moving parts Electric shock, impact, cutting, crushing The device must be disconnected from the mains power supply before any maintenance work. DANGER! Heat transfer liquid drips onto the electronics Short circuit The device must be disconnected from the mains power supply before any maintenance work. CAUTION! Contact with hot / cold device parts, accessories and heat transfer liquid.
Maintenance Interval Maintenance work monthly Inspection of the drain tap by visual inspection from the outside Inspection of the external tubes for material fatigue Cleaning of the condenser (only for air-cooled devices) Cleaning of the water filter (only for water-cooled devices) quarterly Decalcification of the cooling water circuit (a shorter interval must be selected depending on water hardness and operating time) (only for water-cooled devices) half-yearly Inspection of the heat transfer liqui
Maintenance 7.4 Cleaning air-cooled condenser Personnel: Operating personnel 1. Switch off the device. 2. Remove the front panel carefully. Pull the panel to the front by gripping the recess and lift the panel out of the guide for this. The front panel is held in place by a magnetic catch. 3. Brush off or vacuum the condenser. 4. Replace the front cover carefully. Fig. 69: Remove the front panel 7.5 Cleaning water filter Personnel: Operating personnel 1.
Maintenance 7.6 Decalcifying cooling water circuit Personnel: 1. Operating personnel Switch off the device and prepare the decalcification process accordingly. The descaling agent should be fed to the water cooling using a pump or a funnel through the supply tube. The descaling agent return flow should be via flow tube of the water cooling into a container with sufficient capacity (at least 10 litres). LAUDA descaling agent (catalogue number LZB 126, 5 kg packaging) is required for decalcification.
Faults 8 Faults 8.1 Alarms, errors and warnings Any alarms, error signals and warnings triggered on the device are shown as plain text on the screen. Procedure in the event of alarms Alarms are relevant for safety. The components of the device such as the pump switch off. A two-tone signal is output by the device. Alarms can be cancelled with the ENTER button after rectification of the cause of the fault. You can find a list of alarms in Ä Chapter 8.2 ‘Alarm codes’ on page 74.
Faults Code English output Description 15 Digital Input Malfunction at the digital input 20 T ext Ethernet No signal for actual value via the Ethernet module 8.3 Low Level alarm If the liquid level falls below the minimum level, an alarm sounds. Low Level is shown on the screen. The device components such as the pump are switched off by the electronics. Fig. 72: Alarm Low Level Rectifying fault Personnel: Operating personnel 1. Refill lacking heat transfer liquid. 2.
Faults Restarting device 1. Eliminate the cause of the error. 2. After cooling down, lock the display using the OK button. The device restarts. 8.5 Warnings - control system All warnings of the control system start with the prefix 0. The prefix is followed by two other digits. These digits are listed in the following table.
Faults Code English output Description 024 SW Pump 2 old Software version of pump 2 too old 025 SW Pump 3 old Software version of pump 3 too old 026 SW HTC old Software version of high temperature cooler too old 027 SW Ext. Pt100 old Software version of external Pt100 too old 028 SW Ethernet old Software version of Ethernet too old 029 SW EtherCAT old Software version of EtherCAT too old 033 Clock wrong time Internal clock defective; supply with battery was/is interrupted.
Faults 78 Code English output Description 113 SW Cool too old Software version of cooling module too old 114 SW Analog too old Software version of analogue module too old 115 SW Serial too old Software version of serial interface (RS232) too old 116 SW Contact too old Software version of contact module too old 117 SW Valve 0 old Software version of solenoid valve 0 too old 118 SW Valve 1 old Software version of solenoid valve 1 too old 119 SW Valve 2 old Software version of solenoid
Decommissioning 9 Decommissioning 9.1 Draining device Personnel: Operating personnel WARNING! Contact with hot/cold heat transfer liquid Scalding, frostbite Bring the heat transfer liquid to room temperature before darning. Also note the following: Observe the regulations for disposal of the used heat transfer liquid. 1. Switch off the device. 2. Let the device and the heat transfer liquid cool down or heat up to room temperature. 3.
Decommissioning 9.2 Draining condenser (only water-cooled devices) Personnel: Operating personnel 1. Temper the device to approx. 20 °C. Switch off the device. 2. Unscrew the tube at the cooling water inlet from the device. 3. Leave the tube at the cooling water outlet screwed to the device. Insert the other end of the tube into a drain or a container. 4. Remove the water filter from the threaded connection. Clean the water filter and then put it back into the threaded connection.
Disposal 10 10.1 Disposal Disposing of refrigerant The refrigerant must be disposed of in accordance with EC regulations 303/2008/EC in combination with 842/2006/EC. CAUTION! Uncontrolled escape of refrigerant Impact, cutting Do not dispose of any pressurised cooling circuit. The decommissioning is only permitted by a specialist. Refrigerant GWP(100a) R404A 3922 Global Warming Potential (GWP) time horizon 100 years - according to IPCC IV (2007). Comparison: CO2 = 1.0.
Technical data 11 11.1 Technical data General data The device sound pressure level of the devices is below 70 dB. In accordance with EC Directive 2006/42/EC, the sound pressure level of the devices is therefore not specified further.
Technical data Device-specific Operating temperature range Operating temperature range with optional heater Temperature stability Dimensions (W x D x H) Weight °C °C K mm kg VC 600 -20 ... 40 -20 ... 80 ±0.05 350 x 480 x 595 39 VC 1200 -20 ... 40 -20 ... 80 ±0.05 450 x 550 x 650 54 VC 1200 W -20 ... 40 -20 ... 80 ±0.05 450 x 550 x 650 51 VC 2000 -20 ... 40 -20 ... 80 ±0.05 450 x 550 x 650 57 VC 2000 W -20 ... 40 -20 ... 80 ±0.05 450 x 550 x 650 54 VC 3000 -20 ...
Technical data Clearance around the device Exhaust air (aircooled devices) 20/20/0/0 --- 50/50/20/20 4500 20/20/0/0 --- VC 7000 W VC 10000 VC 10000 W Power consumption - VC 600 Alternating current VC 600 Unit 230 V; 50 Hz 0.7 kW 220 V; 60 Hz 0.7 kW 115 V; 60 Hz 0.8 kW 100 V; 50/60 Hz 0.7 kW Power consumption - VC 1200 (W) to VC 3000 (W) Alternating current VC 1200 (W) VC 2000 (W) VC 3000 (W) Unit 230 V; 50 Hz 1.1 1.6 1.8 kW 200 V; 50/60 Hz 1.3 2.0 2.
Technical data Thread G ¾" and olive ½" Cooling capacity Cooling capacity (20 °C) Cooling capacity (10 ℃) Cooling capacity (0 ℃) Cooling capacity (-10 ℃) Cooling capacity (-20 ℃) kW kW kW kW kW VC 600 0.60 0.50 0.36 0.21 0.08 VC 1200 (W) 1.20 1.00 0.70 0.40 0.18 VC 2000 (W) 2.00 1.50 1.06 0.68 0.38 VC 3000 (W) 3.00 2.40 1.68 1.03 0.60 VC 5000 (W) 5.00 3.90 2.75 1.70 1.00 VC 7000 (W) 7.00 5.30 3.70 2.40 1.30 VC 10000 (W) 10.00 7.60 5.30 3.50 2.
Technical data Maximum/minimum filling volume Maximum flow pressure Maximum flow rate Pump connection Drain tap VC 5000 (W) 33/20 3.2 37 G ¾ (15), olive ¾" G ½" VC 7000 (W) 64/48 3.2 37 G 1¼ (20), olive 1" G ¾" VC 10000 (W) 64/48 3.2 37 G 1¼ (20), olive 1" G ¾" Characteristic curves of the standard pumps Fig. 75: Characteristic curves of the standard pumps Pump characteristics for different mains power supply Pump 0.
Technical data Alternating current VC 1200 (W) and VC 2000 (W) 230 V; 50 Hz LWG 176, 177, 182, 183 200 V; 50/60 Hz* LWG 576, 577, 582, 583 208-220 V; 60 Hz LWG 876, 877, 882, 883 * Pump characteristics for 200 V; 60 Hz: 1.2 bar; 28 litres per minute Pump 3.
Technical data Characteristic curves of the optional pumps Fig. 76: Characteristic curves of the optional pumps Option: Pump 3.2 bar; 37 litres per minute Alternating current VC 1200 (W) VC 2000 (W) 230 V; 50 Hz LWZ 1100 LWZ 1101 200 V; 50/60 Hz LWZ 5100 LWZ 5101 208-220 V; 60 Hz LWZ 8100 LWZ 8101 Option: Pump 4.
Technical data Option: Pump 5 bar; 60 litres per minute Three-phase current VC 5000 (W) VC 7000 (W) VC 10000 (W) 400 V; 3/N/PE~50 Hz LWZ 2106 LWZ 2106 LWZ 2106 208-220 V; 3/PE~60 Hz LWZ 3106 LWZ 3106 LWZ 3106 200 V; 3/PE~50/60 Hz* LWZ 4106 LWZ 4106 LWZ 4106 * Pump characteristics for 200 V; 3/PE~50 Hz: 4.3 bar; 60 litres per minute 11.4 Optional heater Heat output and power consumption Alternating current VC 600 Unit Heat output 1.5 kW Power consumption with heater 2.
Technical data Heat output and power consumption Alternating current VC 1200 (W) VC 2000 (W) VC 3000 (W) Unit Heat output 1.5 1.5 1.5 kW Power consumption with heater 2.6 2.6 2.6 kW LWZ 1095 LWZ 1095 LWZ 1095 Heat output 1.1 1.1 1.1 kW Power consumption with heater 2.3 2.3 2.6 kW LWZ 5095 LWZ 5095 LWZ 5095 1.2 - 1.35 1.2 - 1.35 1.2 - 1.35 kW 2.4 2.5 2.8 kW LWZ 8095 LWZ 8095 LWZ 8095 VC 5000 (W) VC 7000 (W) VC 10000 (W) Unit Heat output 4.5 4.5 7.
Technical data 11.
Technical data 11.
Accessories 12 Accessories The following accessories are available for all devices.
General 13 13.1 General Copyright This manual is protected by copyright and is exclusively intended for the purchaser for internal use. The transfer of this manual to third parties, reproductions of any type and form, whether in whole or in part, and the dissemination and/or communication of the contents are not authorised without the written permission of the manufacturer. Infringements will result in legal action for damages. We reserve the right to assert further claims. 13.
General 13.5 EC conformity The device complies with the basic occupational health and safety requirements of the Directives listed below. Machinery Directive 2006/42/EC EMC Directive 2004/108/EC LAUDA DR. R. WOBSER GMBH & CO. KG - Pfarrstraße 41/43 97922 Lauda-Königshofen - Germany VC 600, VC 1200 and VC 1200 W: VC 2000 to VC 10000 W: Variocool The device does not come under the Pressure Equipment Directive 97/23/EC as the device is classified in the area of Article 3.3.
Index 14 Index A Accessories Modules.......................................................... 93 Optional (modules).......................................... 93 Actual bath temperature (screen)......................... 42 Adjusting control parameters external........................................................... 52 internal............................................................ 52 Air-cooled Cleaning condenser........................................ 72 Alarm....................................
Index Softkey bar...................................................... Status display (structure)................................ Displaying serial numbers (device)...................... Disposal Packaging....................................................... Refrigerant...................................................... Disposing of refrigerant........................................ DM water.............................................................. Draining Condenser (water-cooled)..............
Index O Packaging Disposal.......................................................... 81 Personal protective equipment (overview)........... 10 Personnel qualification (overview)....................... 10 Placement Device............................................................. 24 Program Access............................................................ 65 Creating.......................................................... 66 Defining loops.................................................
Index U Unpacking............................................................ 13 USB interface Establishing connection.................................. 30 Install driver..................................................... 30 Water-cooled Draining condenser......................................... 80 X Xp......................................................................... 52 Xpf........................................................................ 53 V Version (software) ........................
BESTÄTIGUNG / CONFIRMATION / CONFIRMATION An / To / A: LAUDA Dr. R. Wobser • LAUDA Service Center • Fax: +49 (0) 9343 - 503-222 Von / From / De : Firma / Company / Entreprise: Straße / Street / Rue: Ort / City / Ville: Tel.
Postfach 1251 97922 Lauda-Königshofen ◦ Germany ◦ Phone: +49 (0)9343 503-0 ◦ Fax: +49 (0)9343 503-222 E-Mail: info@lauda.de ◦ Internet: www.lauda.