Installation Manual

A
C EDB F G
Hydrofarm.com
6
ZONE A OUTPUT SCHEDULE
The PX2 lets you precisely schedule up to six
med output sengs from the xtures during
the light cycle (by waage or percentage).
Checkmarks in front of the six med output
sengs provide the ability to disable or enable.
CHECK = Enabled.
1. Press
and enter the ZONE A OUTPUT
SCHEDULE menu.
2. Press
to cursor through the me and
output sengs.
3. Press
or
to adjust, then press
buon to conrm.
4. Repeat steps 2–3 to set all values.
5. Press
buon to save the sengs.
6. Repeat steps for ZONE B.
IMPORTANT ZONE OUTPUT SCHEDULE NOTES
Output adjustments ONLY take eect according to OUTPUT SCHEDULE and clock seng.
Enabling more OUTPUT SCHEDULE sengs is advisable for greater exibility.
Sunrise and sunset (R/S) me seng can impact OUTPUT SCHEDULE. Ensure these two
sengs do not conict. Example: If R/S is set to 10 minutes, the ming between OUTPUT
SCHEDULE signals should be set no less than 10 minutes.
INSTRUCTIONS
Indicator Meaning
A, C
LED on green: Normal status. Screen display: NML
LED on yellow: Over-temperature dimming protecon. Screen display: DIM
LED ashes red: Over-temperature lamp-o protecon or temperature exceeds 80°C.
Screen display: SOS
LED ashes yellow: Temperature control line is not inserted. Screen display: NO PROBE
B, D
LED LIGHT ON: Lamp on. LED LIGHT OFF: Lamp o.
E
If the ANALOG indicator is on, the controller outputs 0–10V signals for LED, 0–11.5V for HID.
F
If the DIGITAL indicator is on, the controller outputs RS485 signals.
E, F
The ANALOG and DIGITAL indicators are both on.
ZONE A is the analog signal output, and ZONE B is the digital signal output.
G
The output signal mode can be switched by clicking the SET buon with a pen.
LED INDICATORS