SYSTEM SETTINGS
The Systems Sengs screen is where the
controller’s overall seng are dened for
both zones.
1. Press
to cycle to the
SYSTEM SETTING menu.
2. Press
to highlight the value you
want to change. Press
or
to
select the correct seng, then press
to conrm.
Value Opons
Temperature unit F or C
Power unit % or W
Hour format 12H or 24H mode
Time Hours/Minutes (AM/PM will adjust automacally)
Date Month/Day/Year
Reset Resets to factory default sengs
3. Repeat step 2 to set all values.
4. Press
to save the sengs.
ANALOG/DIGITAL SETUP
Before starng the display setup, you
must complete the Analog/Digital setup.
1. Using a pen or other small object,
press the recessed
SET buon
1
to
cycle through the following opons.
1
ANALOG AND DIGITAL SETUP:
Zone A = Analog
Zone B = Digital
DIGITAL SETUP:
Each zone can support a maximum of 256 HID digital
(RS-Protocol) xtures.
ANALOG SETUP:
Each zone can support a maximum of 50 LED or HID
analog (0-10V or 0-11.5V) xtures.