Specifications

87
PowerFlex 700H Variable Frequency AC Drive (VFD) Load Reactor
A load reactor (connecting a reactor on the load side of the drive) should be considered in the following situations:
Multi-motor applications (one drive feeding more than one motor)
A low voltage insulation class motor applied on a long cable length
575V motor applications (other than short cable length applications)
A load reactor is NOT required for applications where:
Line voltage is 230V or less.
A Bulletin 1204 terminator unit is utilized.
An Allen-Bradley controlled matched solution is being applied (a 1850V CIV motor is used for a cable length of
600 ft. (185 m)or less in a 575V application).
Bulletin 2165R - Combination PowerFlex 700 Variable Frequency AC Drive (VFD) with Circuit Breaker Disconnect
and Manual, Isolated Bypass
Nominal Load
HP(kW)
480V 600V
Maximum
Continuous Output
Current (Amperes)
Space Factor
(1)
(1) Adding options may increase the space factor of the unit.
Maximum
Continuous Output
Current (Amperes)
Space Factor
(1)
NEMA Type 1
and 1 w/Gasket
NEMA Type 12 NEMA Type 1
and 1 w/Gasket
NEMA Type 12
0.5 1.1
3.0 3.0
0.75…1 2.1 1.7
3.0 3.0
1.5…2 3.4 2.7
35 3.9
58
3.5 3.5 6.1 3.5 3.5
7.5 11 9
10 14 11
15 22
4.0 17 4.0
20 27 22
25 34 27
30 40
4.5 4.5 32 4.5 4.5
40 52
5.0 5.5 41 5.0 5.5
50 65
5.5 6.0 52
60 77
6.0, 35” W 6.0, 35” W 62 6.0, 35”W 6.0, 35”W
75 96
6.0 35” W, 20” D 6.0 35” W, 20” D 77 6.0, 35”W, 20”D 6.0, 35”W, 20”D
100 125 125
6.0, 45”W, 20”D 6.0, 45”W, 20”D
125 156
6.0 45” W, 20” D 6.0 45” W, 20” D
150 180
6.0 50” W, 20” D 144 6.0, 50”W, 20”D
Bulletin 2160R - PowerFlex 700H Variable Frequency AC Drive (VFD) Load Reactor
Drive Rating
Nominal Horsepower
(1)
(1) The horsepower ratings shown are nominal.
Line
Voltage
Space
Factor
(2)
(2) Adding options may increase the space factor of the unit.
Space Factor Catalog Number
NEMA Type 12
Heavy Duty 150 480
1.5 Available for NEMA Type 1 and Type
1 w/ gasket only
200 480
Normal Duty 200 480