Specifications
56
Miscellaneous Options
Option Description FVNR
2112
2113
Blown Fuse Indicator Lights Option is valid only when 480V and 600V Power Factor Correction Capacitor is selected
480V and 600V Power
Factor Correction
Capacitors
2 kVAR through 40 kVAR in 0.5 space factor. 42.5 kVAR through 50 kVAR in 1.0 space factor. These
capacitors should not be used on motors subject to plugging or jogging. Do not subject
capacitors to repetitive switching where capacitors and motors might be reenergized too quickly
after being de-energized. Do not install capacitors in any vertical section that contains a variable
frequency drive. Capacitors are mounted in separate unit with a separate door. This unit is located
below selected starter. Door interlock is included. Three phase power fuses are included.
Capacitors are factory wired to load side of the contactor and on the line side of the overload
relay.
2…50
kVAR
Miscellaneous Options
Option Description FVC FVR FVNR TS1W
TS2W
2102L
2103L
2106
2107
2112
2113
2122
2123
Grounded Unit Door Hinge mounted ground strap mounted on bottom hinge of unit door.
Unit door hinge grounding strap for IEC requirements.
Available on all units
Unit Load Connector Select on all plug-in units in sections with vertical
unit load ground bus.
Unplated
copper
Available on all plug-in units
Tin plated
copper
Unit Ground Stab Copper unit ground stabs also may be used with
steel vertical ground bus. Select on plug-in units in
sections with vertical plug-in ground bus.
Copper alloy
Available on all plug-in units
Unplated
copper
Tin plated
copper
Thermistor Protection Relay Bulletin 817-E2P, 110 - 120VAC, 50-60 Hz, output is unwired.
Unit Ammeter Analog ammeter and current transformer.
Current transformer only for use with external meter. Current
transformer rated 2.5VA or greater.
Elapsed Time Meter Six digit non-resettable meter (with tenths), mounted in control
station
Unwired Timer Auxiliary (not
available on 0.5 SF units)
Bulletin 596 time delay addition to NEMA size 1
through 5 contactors with N.O. and N.C. contacts.
Not available with -7FEC_ E3.
On delay
Off delay