Specifications

50
Miscellaneous Units
Full section blank mounting plates are six space factors in size. They are available with no disconnect means, fusible
disconnect switch or circuit breaker. They are also available with or without the horizontal bus.
Blank unit doors are available in a range of space factors from 0.5…4.0 in 0.5 space factor increments. The blank unit doors
cover the unused unit space and have a unit support pan.
Empty Unit Inserts
Description
Space Factor
(1)
(1) Adding options may increase the space factor of the unit
Empty Unit Insert For field installed equipment. 8.625 in. working depth with no plug-in stabs. Inserts
come with unit support pan and door. Inserts are NOT UL listed and are NOT CSA
certified.
0.5…4.0
(in 0.5 space factor
increments)
Empty Unit Insert with
Disconnecting Means
For field installed equipment. 8.625 in. working depth and includes fusible
disconnect and plug-in stabs. Inserts come with unit support pan and door. Adding
equipment to this unit insert may require field evaluation by UL/CSA in order to
retain listing/certification.
1.5…4.0
(in 0.5 space factor
increments)
For field installed equipment. 8.625 in. working depth, includes inverse time
(thermal magnetic) circuit breaker and plug-in stabs. Inserts come with unit support
pan and door. Adding equipment to this unit insert may require field evaluation by
UL/CSA in order to retain listing/certification.
1.5…4.0
(in 0.5 space factor
increments)
DeviceNet Units
Description
Space Factor
(1)
(1) Adding options may increase the space factor of the unit
DeviceNet Power Supply Unit
(110…120V AC input and 8.0 A, 24V DC
output)
Without disconnection means, plug-in stabs or control circuit transformer.
Requires separate 110…120V AC source.
0.5
Includes disconnect, fuses and 350VA control circuit transformer to provide power
to power supply.
1.0
Includes circuit breaker, fuses and 350VA control circuit transformer to provide
power to power supply.
Redundant DeviceNet Power Supply Unit
(110…120V AC input and 8.0 A, 24V DC
output)
Without disconnection means, plug-in stabs or control circuit transformer.
Requires separate 110…120V AC source.
1.0
Includes disconnect, fuses and 750VA control circuit transformer to provide power
to power supply.
1.5
Includes circuit breaker, fuses and 750VA control circuit transformer to provide
power to power supply.
ControlNet to DeviceNet linking device
(Bulletin 1788)
Without disconnecting means, plug-in stabs, or control circuit transformer.
Requires separate 110…120V AC source. Viewing window in door to provide visual
verification of network status.
0.5
With disconnect, fuses, and 80VA control circuit transformer. Viewing window in
door to provide visual verification of network status.
1.0
With circuit breaker, fuses, and 80VA control circuit transformer. Viewing window
in door to provide visual verification of network status.
Ethernet to DeviceNet linking device
(Bulletin 1788)
Without disconnecting means, plug-in stabs or control transformer. Requires
separate 110…120V AC source. Viewing window in door to provide visual
verification of network status.
0.5
With fusible disconnect and 80VA control transformer. Viewing window in door to
provide visual verification of network status.
1.0
With circuit breaker and 80VA control transformer. Viewing window in door to
provide visual verification of network status.
External DeviceNet Connector Unit with
remotely powered 120V AC receptacle
Door mounted external DeviceNet connection and 120V AC receptacle for
connection of computer to DeviceNet without having to open doors.
0.5