Panel Board with Main Circuit Breaker (PPAN) - Bulletin 2193PP
Bulletin 2193PP is a plug-in unit panel board with a main circuit breaker. The panel boards are rated for 100 A, 150 A
or 225 A with up to 42 branch circuits. One, two and three pole bolt-on branch circuit breakers are available with ratings
from 15…100 A. The Bulletin 2193PP panel board is suitable for use with 3-phase, 4-wire, solidly grounded, Wye systems
rated 480Y/277V or less. IT may also be used on solidly grounded 3-wire power systems, however, only 2-pole and 3-pole
branch circuit breakers can be used.
Bulletin 2193PP Plug-in Panel Board with Main Circuit Breaker (PPAN)
Main Breaker Trip
Rating (Amperes)
Max. Number of
1-pole Circuit
Breakers
Main Circuit
Breaker Type
Space Factor
(1)
(1) Adding options may increase the space factor of the unit.
IC Rating at 480Y/
277V (rms Sym.)
(2)
(2) This rating can be applied to all branch circuit breakers.
100 18 I3C
2.5 25kA
I6C 65kA
I0C 100kA
150 30 I3C
3.0 25kA
I6C 65kA
I0C 100kA
42 I3C
3.5 25kA
I6C 65kA
I0C 100kA
225 18 JD3D
3.5
35kA
(3)
(3) 35kA series combination rating only when used with 50 A or lower rated branch circuit breakers.
Series combination rating is 22kA when used with branch circuit breakers rated 60 A or higher.
30
42
4.0