Specifications

45
Bulletin 2193M 3-Pole Main Circuit Breaker (MCB), continued
Frame Range of
Available Trips
(Amperes)
Interrupting Capacity Ratings
(rms symmetrical Amperes)
Space Factor
(2)
(2) Adding options may increase the space factor of the unit.
Rating
(Amperes)
Type 208V/240V 380V/400V
415V/480V
600V
800 MDL 400…800 65k 50k 25k
2.5
MDLG 65k 50k 25k
HMDL 100k 65k 35k
HMDLG 100k 65k 35k
NDC 100k 100k 65k
NDCG 100k 100k 65k
MDL HI-MAG 800 42k 35k 22k
1200 ND 600…1200 65k 50k 25k
3.5
NDG 65k 50k 25k
HND 100k 65k 35k
HNDG 100k 65k 35k
NDC 100k 100k 65k
NDCG 100k 100k 65k
ND HI-MAG 1200 65k 50k 25k
2000
(1)
(1) These units only can be used on systems of 65kA available or less. If 100kA is required, contact your local authorized Allen-Bradley
distributor or Rockwell Automation Sales Office.
RD 1200…2000 100k 65k 50k
6.0, 30” W, 20” D
RDG 100k 65k 50k