Feeder and Main Fusible Disconnect Switch Units (FDS, MFDS) - Bulletin 2192F and 2192M
These switches are available with ratings from 30…2000 A. The 2192F is a plug-in unit for ratings up to 200 A and frame
mounted for ratings 400 A and above. The 2192M is frame mounted (rigidly mounted and hardwired) in the structure for
all ratings. The bolted pressure switch design is used for 2192 units rated
600…2000 A.
Select disconnect switch rating based upon 125% of actual load amperes.
Bulletin 2192F Fusible Disconnect Switch—Feeders (FDS)
Switch Rating
(Amperes)
Fuse Clip Load Lugs Provided
Space Factor
(1)
(1) Adding options may increase the space factor of the unit.
Rating (Amperes) Class Cables/ Phase Cable/Wire Size Range Wire Type
30 30 CC, J 1 #14-#8 AWG CU
0.5
30 30 CC, J, R, H #14-#4 AWG
1.0
60 60 J, R, H
1.0
Dual 30 30
Dual 60/30 60/30
Dual 60 60
Dual 100/30 100/30 #14-1/0 AWG
#14-4 AWG
1.5
Dual 100/60 100/60
Dual 100 100 #14-1/0 AWG
100 100 #8-1/0 AWG
200 200 #6-4/0 AWG
2.0
400 400 2 #1/0-250 kcmil
2.5
600 600 J, R, H, L 2 #2-600 kcmil CU/AL
3.5
800 800 L 3 #6-350 kcmil
3.5
1200 1200 4 #6-350 kcmil
3.5
Bulletin 2192M Fusible Disconnect Switch—Mains (MFDS)
Switch Rating
(Amperes)
Fuse Clip Line Lugs Provided
Space Factor
(1)
(1) Adding options may increase the space factor of the unit.
Rating
(Amperes)
Class Cables/Phase Cable/Wire
Size Range
Wire Type
30 30 J, R, H 1 #14-#8 AWG CU
1.5
60 60 1 #14-#6 AWG CU
100 100 1 #8-1/0 AWG CU
200 200 1 #6-4/0 AWG CU
2.0
400 400 2 1/0-250 kcmil CU
2.5
600 600 J, R, H, L 2 #2-600 kcmil CU/AL
3.5
800 800 L 3 #6-350 kcmil CU/AL
1200 1200 4 #6-350 kcmil CU/AL
1600 1600 4 #2-600 kcmil CU/AL
6.0,
20” D, 35” W
2000 2000 6 #2-600 kcmil CU/AL