Specifications

41
Lug Compartments for Inside Corner, 10” Wide Sections
and Neutrals/Incoming Line and Outgoing Feeders
Rating
(Amperes)
Cable Provisions
Maximum Number Per Phase and Maximum
Cable Size
Space Factor
(1)
(1) Adding options may increase the space factor of the unit.
Mechanical Type Lugs
Single Cable Lug Crimp Type Lugs
INSIDE CORNER SECTION
600…2000 (4) 800 kcmil (4) 750 kcmil
6.0
10” WIDE SECTION
600…1200 Not Applicable (2) 750 kcmil
(4) 500 kcmil
6.0
Lug Compartments/Incoming Lines Metering Options
Meter Type
(1)
(1) Metering not available in 2191M 600 A main lugs in horizontal wireway.
Description
Analog Ammeter Includes one current transformer and panel type
ammeter.
Current transformers shipped loose with hardware
and mounting instructions
Analog Ammeter with Ammeter
Switch
Includes two current transformers, panel type ameter,
and ammeter switch. Use on three-phase, three-wire
systems only.
Includes three current transformers, panel type
ammeter, and ammeter switch. Use on three-phase,
three-wire systems only.
Analog Voltmeter Includes one fused potential transformers (mounted in a compartment) and panel-type voltmeter.
Analog Voltmeter with Voltmeter
Switch
Includes two fused potential transformers (mounted in a compartment), panel-type voltmeter, and voltmeter
switch. For three-phase, three-wire systems only.
Analog Ammeter and Voltment with
Switches
Two current transformers, panel type ammeter with
ammeter switch, two fused potential transformers, and
panel type voltmeter with voltmeter switch.
Current transformers shipped loose with hardware
and mounting instructions. Use on three-phase,
three-wire systems only.
Three current transformers, panel type ammeter with
ammeter switch, two fused potential transformers, and
panel type voltmeter with voltmeter switch.
Bulletin 1404-M5 Powermonitor 3000
with RS-485 Communication
(2)
(2) For three-wire power systems where L1-N, L1-G, L2-N, L2-G, L3-N, or L3-G may exceed 347V. Contact your local authorized Allen-Bradley distributor or
Rockwell Automation Sales Office for more information.
Display module mounted on door. Includes control circuit transformer. For three-phase, three-wire systems,
three current transformers ship loose with hardware and mounting instructions. For three-phase, four-wire
systems, four current transformers ship loose with hardware and mounting instructions. Disconnect switch is
not included.
Bulletin 1404-M6 Powermonitor 3000
with RS-485 Communication
(2)
Bulletin 1405-M610 Digital Volt/
Ammeter
For use on three-phase, three-wire systems only. Plug-in metering unit with disconnect and fuses. Current
transformers shipped loose with hardware and mounting instructions. Potential transformers are internal to
the device.