Specifications
38
Metering Units
Metering Compartments - Bulletin 2190
Bulletin 2190 metering units are used for power management of three-phase
systems and include analog ammeter and voltmeter, Powermonitor II and
Powermonitor 3000 units. The ammeter, voltmeter, digital meter and
Powermonitor 3000 units include a 30 A fused disconnect switch.
Bulletin 2190 - Analog Metering Compartments
Meter Type Description Line Voltage (Volts)
Space Factor
(4)
(4) Adding options may increase the space factor of the unit.
Door Mounted Analog
Ammeter
(1)
(1) No disconnect means, no unit insert
One current transformer and panel type ammeter. 600 Max.
0.5 or 1.0
Door Mounted Analog
Ammeter with Ammeter
Switch
(1)(2)
(2) Use on 3-phase, 3-wire systems only
Two or three current transformers, panel type ammeter and
ammeter switch.
0.5 or 1.0
Plug-in Analog Ammeter
and Voltmeter with
Switches
(2)(3)
(3) Units with disconnect and fuses
Two or three current transformers, panel type ammeter with
ammeter switch, two (2) fused potential transformers and panel type
voltmeter with voltmeter switch.
208…600
1.0
Bulletin 2190 - Digital Metering Compartments
Meter Type Description Space
Factor
(2)
(2) Adding options may increase the space factor of the unit.
Powermonitor 3000, (Bulletin
1404-M5), with RS-485
Communications
Plug-in unit with disconnect, fuses, and control circuit transformer. Fused potential transformers are
self-contained in the meter’s power module.
1.0
Powermonitor 3000, (Bulletin
1404-M6) with RS-485
Communication
Digital Volt and Ammeter,
(Bulletin 1405-M610)
(1)
(1) For use on 3-phase, 3-wire systems only
Plug-in metering unit with disconnect and fuses.
0.5