Specifications

35
Space Saving NEMA - Combination Full Voltage Non-Reversing Starter Units (FVNR) -
Bulletin 2112 and 2113
These combination full voltage non-reversing starter units offer a space saving
alternative while utilizing an Allen-Bradley Bulletin 300 starter and either a fused
disconnect or a circuit breaker. The Bulletin 2112 Space Saving NEMA non-reversing
starter units are rated for NEMA Size 1 applications and the Bulletin 2113 Space Saving
NEMA non-reversing starter units are rated for NEMA Size 1 through 4 applications. Each
unit is provided as a NEMA Class I, Type B-D unit with terminals mounted in the unit for
connections to remote devices. These full voltage non-reversing units are available with
E1 Plus or E3 electronic overload relays.
Bulletin 2112 and 2113 - Space Saving NEMA Full Voltage Non-reversing Starter Unit with Fused Disconnect Switch
or Circuit Breaker (FVNR)
NEMA Size Horsepower Bulletin 2112 Bulletin 2113
480V 600V
Fuse Clip
Space Factor
(1)
(1) Adding options may increase the space factor of the unit.
Circuit Breaker
Type
Space Factor
(1)
Rating
(Amperes)
Class
1 0.5…10 0.75…10
30 CC, J, HRCII-C 0.5 MCP, I3C, I6C 0.5
2 15…25 15…25
0.5
3 30 …50 30…50
1.0
4 60…100 60…100
MCP, JD3D,
JD6D
1.0