Specifications

34
Combination Vacuum Full Voltage Non-reversing Starter Units (FVNR) - Bulletin 2112 and 2113
These combination full voltage non-reversing starter units are supplied with an Allen-Bradley Bulletin 1102C contactor
and either a fusible disconnect or a circuit breaker. The full voltage non-reversing vacuum starters are rated 200 A, 400 A or
600 A. Each unit is provided as a NEMA Class 1, Type B unit, with terminals mounted in the unit for connection to remote
devices. Full voltage non-reversing vacuum starter units are available with a eutectic alloy, E1 Plus or E3 electronic
overload relay.
Bulletin 2112 and 2113 Vacuum Full Voltage Non-reversing Starter Unit with Vacuum Contactor and Fusible
Disconnect Switch or Vacuum Contactor and Circuit Breaker (FVNR)
Rating
(Amperes)
Horsepower Disconnect
Switch
Rating
(Amperes)
Bulletin 2112 Bulletin 2113
208V 240V 380…
415V
480V 600V
Fuse Clip Space
Factor
(1)
(1) Adding options may increase the space factor of the unit.
Circuit
Breaker
Frame
(Amperes)
Space
Factor
(1)
Rating
(Amperes)
Fuse
Class
200 40…50 40…60 60…100 60…125 60…150 200
100 J, R, H,
HRCII-C
3.5 250AF 3.5
200 J, R, H,
HRCII-C
400 J
60 75 150 200 400
200 J, R, H,
HRCII-C
4
400 J
400 75…100 100 125…200 200 250…300 400
200 J, R, H,
HRCII-C
4.5 250AF 3.5
400 J, R, H,
HRCII-C
400AF 3.5
600 J 600AF 4
125 125…150 250 250…300 350…400 600
400 J, R, H,
HRCII-C
6.0,
20”W
6.0, 20”W
600 J
600 150 300 350 600
400 J, R, H,
HRCII-C
6.0,
20”W
600AF 6.0, 20”W
600 J