Specifications

33
Combination Full Voltage Non-reversing Starter Units (FVNR) - Bulletin 2112 and 2113
These combination full voltage non-reversing starter units are supplied with an
Allen-Bradley Bulletin 509 starter and either a fusible disconnect or a circuit breaker. The
full voltage non-reversing starters are rated for NEMA sizes 1 through 6. Each unit is
provided as a NEMA Class I, Type B-T unit, with terminals mounted in the unit for
connection to remote devices. Full voltage non-reversing starter units are available with
a eutectic alloy, E1 Plus or E3 electronic overload relay.
Bulletin 2112 and 2113 - Full Voltage Non-reversing Starter Units with Fusible Disconnect Switch or
Circuit Breaker (FVNR)
NEMA Size Horsepower Bulletin 2112 Bulletin 2113
208V 240V 380…415V 480/600V
Fuse Clip Space
Factor
(1)
(1) Adding options may increase the space factor of the unit.
Circuit
Breaker
Frame
Space
Factor
(1)
Rating
(Amperes)
Class
1 0.125…5 0.125…5 0.125…10 0.125…10
30 CC, J, HRCII-C 0.5 MCP, I3C,
I6C
0.5
1 0.125…7.5 0.125…7.5 0.125…10 0.125…10
30 CC, J, R, H,
HRCII-C,
1.0 MCP,
MCP-ELC,
I3C, I3C-CL,
I6C
1.0
60 J, R, H, HRCII-C
DUAL 1 0.125…7.5 0.125…7.5 0.125…10 0.125…10
MCP, I3C,
I6C
1.5
2 10 10…15 15…25 15…25
30
60
100
J, R, H, HRCII-C
J, R, H, HRCII-C
J, HRCII-C
1.0 MCP,
MCP-ELC,
I3C, I3C-CL,
I6C
1.0
100 R, H 1.5
DUAL 2 10 10…15 15…25 15…25
MCP, I3C,
I6C
1.5
3 15…25 20…30 30…50 30…50
60
100
200
J
J
J
2.0 MCP,
MCP-ELC,
I3C, I3C-CL,
I6C
1.5
60
100
200
R, H, HRCII-C
R, H, HRCII-C
R, H, HRCII-C
2.5
4 30…40 40…50 60…75 60…100
100
200
400
J, HRCII-C
J, HRCII-C
J
2.5 MCP,
MCP-ELC,
JD3D, JD6C
2.0
100, 200 R, H R, H 3.0
5 50…75 60…100 100…150 125…200
200
400
600
J
J
J
3.5 MCP, JD3D,
K3D, JD6D,
K6D
3.5
200
400
R, H, HRCII-C
R, H, HRCII-C
4.0
6 100…150 125…200 200…300 250…400
400
600
800
R, H
J, R, HRCII-C
L
6.0 25” W MCP, LD,
HLD
6.0 25” W
400, 600,
800
R, H J, R, HRCII-C L